A simple building has two types of spaces: perimeter and interior. These two
space types require different types of VAV terminal units to satisfy their
requirements. It is important to realize that many VAV systems include a
combination of different types of terminal units based on individual space
requirements.
The VAV supply fan capacity is modulated in response to changing building
loads. Four methods of modulating fan capacity include: discharge dampers,
inlet vanes, fan speed control, and variable-pitch blade control.
Fan capacity is also controlled based on the static pressure in the system. There
are three common methods for sensing and controlling system static pressure:
fan outlet static-pressure control, supply duct static-pressure control, and
optimized static-pressure control.