period two
Components of a VAV System
Similar to electronic control, an electronic pressure transducer enables
pressure-independent control of the VAV terminal unit. The digital controller
positions the modulation device and operates the fan and the heat source.
Minimum and maximum airflow settings are adjusted through a
communication link to the digital controller. A 24-volt power supply is required
to power the unit actuator and controls.
Direct Digital Control (DDC)
Electronic pressure transducer provides
pressure-independent control
Digital controller positions modulation device,
controls terminal fan and heat source
Minimum and maximum airflow settings
adjusted through communication link
Electric power supply operates modulation
device and electronic controller
Figure 47