Maintenance Considerations
The American Society of Heating, Refrigerating and Air Conditioning Engineers
(ASHRAE) has published Guideline 3 titled
Reducing Emission of Halogenated
Refrigerants in Refrigeration and Air Conditioning Equipment and Systems
.
This guideline includes a recommended list of data points to be logged daily for
each chiller. Much of this data may be available through the chiller’s control
panel.
Special attention should be given to the following:
Review the operating log and trends
Measure the oil pressure drop to determine if the oil filter needs to be
replaced
Measure refrigerant superheat and subcooling
Measure both the refrigerant and oil charges
operating log
ASHRAE Guideline 3
Chilled water inlet and outlet
temperatures and pressures
Chilled water flow
Evaporator refrigerant
temperature and pressures
Evaporator approach
temperature
Condenser water inlet and
outlet temperatures and
pressures
Condenser water flow
Condenser refrigerant
temperature and pressures
Condenser approach
temperature
Compressor refrigerant suction
and discharge temperatures
Refrigerant level
Oil pressures, temperature, and
levels
Addition of refrigerant
Addition of oil
Vibration levels
Figure 39