Compressor Capacity Control
At full load, the slide valve is closed. The compressor pumps its maximum
volume of refrigerant, discharging it through both the radial and axial ports.
At part load, the slide valve modulates toward the open position. The opening
created by the valve movement allows refrigerant vapor to bypass from the
rotor pockets back to the suction side of the compressor. This reduces the
volume of vapor available for the compression process. It also reduces the
amount of rotor length available for compression. In this manner, the volume of
refrigerant that is pumped by the compressor is varied, unloading it to balance
the existing chiller load.