Absorption Chiller Types
notes
The high-temperature generator pump draws a portion of the intermediate
solution from the low-temperature generator and delivers it to the high-
temperature generator to be reconcentrated.
This cooler intermediate solution passes through the high-temperature heat
exchanger to be preheated by the hot concentrated solution returning from the
high-temperature generator. This reduces the heat energy required to boil the
refrigerant inside the high-temperature generator. Precooling the concentrated
solution returning to the absorber reduces the flow rate of cooling water
required through the absorber.
The precooled, concentrated solution leaving the high-temperature heat
exchanger then mixes with the rest of the intermediate solution that is returning
from the low-temperature generator, before traveling to the low-temperature
heat exchanger.