Absorption Chiller Types
separate from the absorbent solution. As the refrigerant boils away, the
solution becomes concentrated and returns to the absorber.
The hot refrigerant vapor produced in the high-temperature generator migrates
to the low-temperature generator where it flows through the tubes that are
immersed in a dilute solution. The solution absorbs heat from the high-
temperature refrigerant vapor, causing the refrigerant in the low-temperature
generator to boil and separate from the absorbent solution. As that refrigerant
boils away, the concentration of the solution increases and it returns to the
absorber.
The low-temperature refrigerant vapor produced in the low-temperature
generator migrates to the cooler condenser. Additionally, the liquid refrigerant
that condensed inside the tubes of the low-temperature generator flows into
the condenser.
Next, the refrigerant travels through the condenser, expansion device,
evaporator, and absorber in a manner similar to refrigerant travel in the
indirect-fired double-effect absorption chiller.
The low-temperature generator pump returns the dilute absorbent solution
to the low-temperature generator to be reconcentrated. This cool dilute solution
passes through the low-temperature heat exchanger to be preheated by the
hot concentrated solution returning from the two generators.
condenser
condenser
low
low
-
-
temperature
temperature
generator
generator
evaporator
evaporator
absorber
absorber
expansion
expansion
device
device
low
low
-
-
temperature
temperature
heat exchanger
heat exchanger
evaporator spray pump
evaporator spray pump
low
low
-
-
temperature
temperature
generator pump
generator pump
absorber
absorber
spray pump
spray pump
chilled
chilled
water
water
cooling
cooling
water
water
Figure 33