Trane trg-trc001-en Air Conditioner User Manual


 
TRG-TRC001-EN 59
1 93 grains/lb, 64.8°F DP
2 49.5% RH, 70.5°F WB
3 85°F DB, 110 grains/lb
4 41% RH, 64°F WB
5 56°F DP, 32% RH
6a
95°F × 0.20 = 19°F
80°F × 0.80 = 64°F
Mixed-Air Temperature = 19°F + 64°F = 83°F
b See Figure 90.
c 69.4°F WB
7a
95°F × 0.15 = 13.5°F
78°F × 0.85 = 66.3°F
Mixed-Air Temperature = 13.5°F + 66.3°F = 79.8°F
b See Figure 91.
c 67.4°F WB (See Figure 91.)
4,000 cfm
20,000 cfm

0.20=
)
)
)
)
)
)
)
)
Figure 90
6,000 cfm
40,000 cfm

0.15=
Answers