Trane TCONT800AS11AA Air Conditioner User Manual


 
TCONT800AS11AA TOUCH SCREEN PROGRAMMABLE COMFORT CONTROL
69-1787-1 8
Pub. No. 18-HD25D18-1
Continuous
Backlight
0280 0 Backlight not on
continuously.
Comfort control
backlight comes
on with each key
press.
1 Backlight is on continuously
(comfort control must have a
common wire attached for
this function).
Option is always
shown; however,
continuously on
backlight works
only if comfort
control is wired
with 24 Vac
Common.
Changeover 0300 0 Manual changeover 1 1—auto changeover
Deadband 0310 3 Heating and cooling
setpoints can be set
no closer than
3
°
F (1.5
°
C)
2 thru 9 Heating and cooling
setpoints can be set no
closer than chosen
value:
2—2
°
F (1
°
C)
3—3
°
F (2
°
C)
4—4
°
F (2.5
°
C)
5—5
°
F (3
°
C )
6—6
°
F (3.5
°
C)
7—7
°
F (4
°
C)
8—8
°
F (4.5
°
C)
9—9
°
F (5
°
C)
Shown only if
automatic
changeover is
selected.
Temperature
Indication
Scale
0320 0 Temperature is
displayed in
°
F.
1 Temperature is displayed
in
°
C.
Daylight
Savings
0330 1 Daylight savings
enabled (United
States).
0 0—daylight savings is
disabled.
Set to 0 in areas
that do not follow
daylight savings.
Remote
Temperature
Sensor
(Outdoor or
Indoor)
0340 0 No remote
temperature sensor
1,3 1—outdoor temperature
sensor for display only.
3—indoor temperature
sensor.
Defaults and
Options depend
on System Type
selected. Indoor
Temperature
Sensor uses an
averaging
network and does
not include on-
board sensor.
Furnace Filter
Change
Reminder
0500 0 Furnace filter
change reminder off
1-6 1—10 r un t i m e d ays
2—30 ru n t im e da ys
3—60 ru n tim e da ys
4—90 ru n t im e da ys
5—1 20 r un ti me da ys
6—36 5 r un tim e d ay s
Run time based
on call for fan.
Humidifier
Pad
Replacement
Reminder
0510 0 Humidifier pad
replacement
reminder off
1-3 1—90 calendar days
2—180 calendar days
3—3 65 c al en da r d ay s
Table 4. Installer Setup Menu. (Continued)
Select
Installer
Setup
Number
Factory Setting Other Choices
CommentsOption Description Options Description