Trane TCONT800AS11AA Air Conditioner User Manual


 
TCONT800AS11AA TOUCH SCREEN PROGRAMMABLE COMFORT CONTROL
7 69-1787-1
Pub. No. 18-HD25D18-1
IMPORTANT
The Installer Setup Menu (Table 4) shows all available options. These options customize themselves as you
make selections to Installer Setup. So not all Installer Setup Selections are shown or are available
to change.
Table 4. Installer Setup Menu.
Select
Installer
Setup
Number
Factory Setting Other Choices
CommentsOption Description Options Description
Not used. 1 thru 0099
Date (Year
Upper)
0120 20 Set first two digits of
current calendar
year (20 for year
2005, etc)
21 21 —first two digits of
current calendar year (21xx)
2000 -2178
available
Date (Year
Lower)
0130 05 Represents last two
digits of current
calendar year
(2005).
00 -99 Select last two digits of
current calendar year.
2000 -2178
available
Date (Month) 0140 6 Digit(s) represents
current calendar
month.
1-12 Select number that
represents current calendar
month.
Date
(Day)
0150 15 Digit(s) represents
current calendar
date.
1-31 Select number that
represents current calendar
date.
Schedule
Options
0160 4 7-day programming 0 0 —nonprogrammable
System Type
Selection
0170 1 1 Heat/1 Cool
System
1-6 1—1 heat/1 cool
2—single-stage heat pump
(no aux. heat)
3—heat only (no fan)
4 —heat only (with fan)
5—hot water Series 20
(3-wire or normally open
zone valves)
6—cool only
Available options
and defaults vary
by comfort
control. System
selection
automatically
modifies some
default settings
and/or hides other
Installer Setup
options.
Fan Operation 0180 0 Heat/cool appli-
cations where
equipment controls
fan operation in
heat mode.
1 Heat pump or electric heat
applications where comfort
control controls fan
operation in heat mode.
Only shown if
heat/cool system
is selected. If heat
pump is chosen,
fan defaults to
electric.
Cycles per
hour (cph) for
1st Stage
Compressor
0220 3 Compressor Stage
1 cycles per hour
(cph)
1-6 1-6 available;
3 is recommended.
Cycles per
hour (cph) for
Heater
Stage 1
0240 5 Heater Stage 1
cycles per hour
(cph).
1-12 1-12 available; typical
s et t in gs :
1—1 cph used for steam or
gravity system.
3—3 cph used for 2-stage
fossil fuel forced air systems
or hot water systems.
5—5 cph used for single-
stage fossil fuel forced air
systems.
9—9 cph used for electric
forced air heat systems
(electric auxiliary heat for
heat pump systems).
Not shown if
system selection
is heat pump.
Selection in this
stage changes
default cph for
2nd stage heat.