Trane RT-PRC007-EN Air Conditioner User Manual


 
33RT-PRC007-EN
Electrical
Data
Table ED-2 27½-50 Ton Electrical Service Sizing Data
1
Fan Motors
Compressor Supply Condenser Exhaust
Allowable Standard/
Electrical Voltage RLA LRA Hi-Efficiency FLA FLA
Model Characteristics Range No/Ton (Ea.) (Ea.) HP FLA No. HP (Ea.) No. HP (Ea.)
TC/TE/YC*330 208/60/3 187-229 1/10,1/15 41.9/62.8 269/409 7.5 22.3/21.5 3 1.1 7.0 2 1.0 6.7
10.0 29.7/29.0
230/60/3 207-253 41.9/62.8 247/376 7.5 19.6/18.8 7.0 6.7
10.0 26.4/25.2
460/60/3 414-506 18.1/27.3 95/142 7.5 9.8/9.4 3.5 2.9
10.0 13.2/12.6
575/60/3 517-633 14.6/21.8 76/114 7.5 7.8/7.5 2.8 2.3
10.0 10.3/10.1
TC/TE/YC*360 208/60/3 187-229 2/15 62.8 409 7.5 22.3/21.5 3 1.1 7.0 2 1.0 6.7
10.0 29.7/29.0
230/60/3 207-253 62.8 376 7.5 19.6/18.8 7.0 6.7
10.0 26.4/25.2
460/60/3 414-506 27.3 142 7.5 9.8/9.4 3.5 2.9
10.0 13.2/12.6
575/60/3 517-633 21.8 114 7.5 7.8/7.5 2.8 2.3
10.0 10.3/10.1
TC/TE/YC*420 208/60/3 187-229 2/15 62.8 409 7.5 22.3/21.5 3 1.1 7.0 2 1.0 6.7
10.0 29.7/29.0
15.0 44.4/41.5
230/60/3 207-253 62.8 376 7.5 19.6/18.8 7.0 6.7
10.0 26.4/25.2
15.0 38.6/36.0
460/60/3 414-506 27.3 142 7.5 9.8/9.4 3.5 2.9
10.0 13.2/12.6
15.0 19.3/18.0
575/60/3 517-633 21.8 114 7.5 7.8/7.5 2.8 2.3
10.0 10.3/10.1
15.0 15.4/14.5
TC/TE/YC*480 208/60/3 187-229 2/15,1/10 62.8/62.8/41.9 409/409/269 10.0 29.7/29.0 4 1.1 7.0 2 1.0 6.7
15.0 44.4/41.5
230/60/3 207-253 62.8/62.8/41.9 376/376/247 10.0 26.4/25.2 7.0 6.7
15.0 38.6/36.0
460/60/3 414-506 27.3/27.3/18.1 142/142/95 10.0 13.2/12.6 3.5 2.9
15.0 19.3/18.0
575/60/3 517-633 21.8/21.8/14.6 114/114/76 10.0 10.3/10.1 2.8 2.3
15.0 15.4/14.5
TC/TE/YC*600 208/60/3 187-229 3/15 62.8 409 10.0 29.7/29.0 4 1.1 7.0 2 1.0 6.7
15.0 44.4/41.5
20.0 58.7/56.1
230/60/3 207-253 62.8 376 10.0 26.4/25.2 7.0 6.7
15.0 38.6/36.0
20.0 51.0/49.4
460/60/3 414-506 27.3 142 10.0 13.2/12.6 3.5 2.9
15.0 19.3/18.0
20.0 25.5/24.7
575/60/3 517-633 21.8 114 10.0 10.3/10.1 2.8 2.3
15.0 15.4/14.5
20.0 20.4/19.6
Notes:
1. All customer wiring and devices must be installed in accordance with local and national electrical codes.