Trane PKG-PRC007-EN Air Conditioner User Manual


 
PKG-PRC007-EN42
Table ED-6 — Genius – Electrical Features - SAVE 050
Nominal Operation Values Compressor Fan Motor Consumption Current
Fan Voltage KW CNO KW CNO KW A
STD 220V 14.10 3.04 17.14
and 380V 4.17 8.16 0.83 1.76 5.00 9.92
Option 1 440V 7.05 1.52 8.57
220V 14.10 4.14 18.24
Option 2 380V 4.17 8.16 1.22 2.39 5.39 10.55
440V 7.05 2.07 9.12
Plenum Box 220V 14.10 1.80 15.90
Option 380V 4.17 8.16 0.45 1.04 4.62 9.20
440V 7.05 0.90 7.95
Maximum operation values Compressor Fan Motor Current
Fan Voltage CMO CMO A
STD 220V 19.80 3.80 23.60
and 380V 11.46 2.19 13.65
Option 1 440V 9.90 1.90 11.80
220V 19.80 5.18 24.98
Option 2 380V 11.46 2.99 14.45
440V 9.90 1.90 11.80
Plenum Box 220V 19.80 2.25 22.05
Option 380V 11.46 1.30 12.76
440V 09.90 1.13 11.03
Start-up values Compressor Fan Motor
Fan Voltage LRA LRA
STD 220V 128.00 21.96
and 380V 74.11 12.68
Option 1 440V 64.00 10.98
220V 128.00 21.96
Option 2 380V 74.11 17.85
440V 64.00 10.98
Plenum Box 220V 128.00 11.25
Option 380V 74.11 6.50
440V 64.00 5.63
To know which ventilation option should be used, consult the behavior of the
ventilation options.
CNO = Nominal operation current (A).
CMO = Maximum operation current.
LRA = Locked rotor amps.
STD Option and Option 1 - evaporator fan motor -1 CV.
Option 2 - evaporator fan motor -1.5 CV.
Plenum box option - evaporator fan motor -0.5 CV.
Size the electrical wiring using the maximum operation currents.
Electrical
Data