Trane PKG-PRC007-EN Air Conditioner User Manual


 
PKG-PRC007-EN24
Table PD-10 — Gross Cooling Capacities SAVE-150 English
ENT Water Temp (°F)
75 85
Entering Wet Bulb Temperature (°F)
Ent. 61 67 73 61 67 73
DB
CFM (°F) TGC SHC GPM TGC SHC GPM TGC SHC GPM TGC SHC GPM TGC SHC GPM TGC SHC GPM
75 165.6 138.7 37.9 185.4 106.0 41.4 206.9 72.8 45.8 160.4 136.3 37.4 179.6 103.6 41.4 200.2 70.4 45.4
5400 80 167.7 163.2 38.3 185.2 132.7 41.4 206.6 99.4 45.8 163.0 160.0 37.9 179.3 130.3 41.4 200.0 97.1 45.4
85 175.0 173.4 39.6 185.1 154.9 41.4 206.4 121.6 45.8 170.6 169.0 39.6 179.3 152.4 41.4 199.9 119.2 45.4
90 183.4 181.7 41.0 186.5 175.6 41.9 206.3 143.5 45.8 178.8 177.1 41.0 181.0 172.6 41.4 199.7 141.2 45.4
75 167.6 143.7 38.3 187.5 108.8 41.9 209.1 73.5 46.3 162.3 141.2 37.9 181.3 106.4 41.4 202.3 71.1 45.8
5850 80 170.7 168.2 38.8 187.3 137.3 41.9 208.8 101.9 46.3 166.0 164.3 38.8 181.2 135.1 41.4 202.1 99.5 45.8
85 179.0 177.3 40.5 187.3 160.8 41.9 208.6 125.4 46.3 174.4 172.7 40.1 181.4 158.2 41.4 202.0 123.0 45.8
90 187.6 185.8 41.9 189.4 182.0 42.3 208.5 148.8 46.3 182.9 181.2 41.9 183.9 178.8 42.3 201.8 146.4 45.8
75 169.5 148.4 38.3 189.3 111.5 42.3 210.9 74.3 46.7 164.1 145.8 38.3 183.2 109.1 41.9 204.1 71.9 46.3
6300 80 173.8 172.1 39.2 189.2 141.6 42.3 210.8 104.3 46.7 169.2 167.5 39.2 183.0 139.2 41.9 203.9 101.9 45.8
85 182.6 180.9 41.0 189.4 166.4 42.3 210.6 129.2 46.7 177.8 176.1 41.0 183.4 163.7 41.9 203.8 126.8 45.8
90 191.4 189.6 42.7 192.3 187.6 42.7 210.5 154.0 46.7 186.5 184.7 42.7 186.8 184.0 42.7 203.7 151.6 45.8
75 171.2 152.9 38.8 191.0 114.2 42.7 212.7 74.9 46.7 164.1 150.2 38.8 184.8 111.7 42.3 205.8 72.6 46.3
6750 80 176.8 175.1 40.1 190.8 145.9 42.7 212.5 106.6 46.7 172.1 170.5 39.6 184.6 143.4 42.3 205.6 104.2 46.3
85 185.9 184.1 41.9 191.3 171.7 42.7 212.4 132.8 46.7 180.9 179.2 41.4 185.3 169.0 42.3 205.4 130.4 46.3
90 194.9 193.0 43.6 195.1 192.5 43.6 212.2 158.9 46.7 189.8 188.0 43.2 189.7 187.9 43.2 205.3 156.5 46.3
Table PD-10 — Gross Cooling Capacities SAVE-150 (Cont.)
ENT Water Temp (°F)
95
Entering Wet Bulb Temperature (°F)
Ent. 61 67 73
DB
CFM (°F) TGC SHC GPM TGC SHC GPM TGC SHC GPM
75 155.0 133.7 37.4 173.4 101.1 41.0 193.4 68.0 44.9
5400 80 158.0 156.2 37.9 173.3 127.8 41.0 193.2 94.6 44.9
85 165.9 164.3 39.6 173.4 149.8 41.0 193.1 116.8 44.9
90 174.0 172.3 41.0 175.4 169.5 41.4 192.9 138.7 44.9
75 156.8 138.5 37.9 175.2 103.9 41.4 195.3 68.7 45.4
5850 80 161.3 159.7 38.8 175.0 132.3 41.4 195.2 97.1 45.4
85 169.6 168.0 40.1 175.4 155.6 41.4 195.0 120.6 45.4
90 177.9 176.2 41.9 178.3 175.0 41.9 194.9 144.0 45.4
75 158.4 143.1 37.9 176.8 106.6 41.4 197.0 69.5 45.8
6300 80 164.3 162.8 39.2 176.7 136.7 41.4 196.9 99.4 45.8
85 172.8 171.2 41.0 177.2 161.0 41.9 196.7 124.4 45.4
90 181.3 179.6 42.3 181.3 179.5 42.3 196.6 149.1 45.4
75 160.0 147.4 38.3 178.3 109.2 41.9 198.6 70.1 45.8
6750 80 167.2 165.6 39.6 178.1 140.9 41.9 198.3 101.7 45.8
85 175.8 174.1 41.4 179.0 166.1 42.3 198.2 127.9 45.8
90 184.5 182.7 43.2 184.5 182.7 43.2 198.0 154.0 45.8
Notes:
TGC = Total Gross Capacity (MBh)
SHC = Sensible Heat Capacity (MBh)
Performance
Data
Water Cooled
60 Hz
Capacity Correction Factor Table
Delta T
Water Total Cap. Sens. Cap.
(°F) GPM MBh MBh
4.5 2.21 1.01 1.01
7.2 1.39 1.01 1.01
10.0 1.00 1.00 1.00
12.6 0.79 0.99 1.00
15.3 0.66 0.99 1.00
18.0 0.56 0.98 0.99