Trane PKG-PRC007-EN Air Conditioner User Manual


 
PKG-PRC007-EN44
Table ED-8 — Genius – Electrical Features - SAVE100
Nominal Operation Values Compressor 1 Compressor 2 Fan Motor Consumption Current
Fan Voltage KW CNO KW CNO KW CNO KW A
220V 14.10 14.10 4.14 32.34
STD 380V 4.17 8.16 4.17 8.16 1.22 2.39 9.56 18.71
440V 7.05 7.05 2.07 16.17
220V 14.10 14.10 5.53 33.73
Option 1 380V 4.17 8.16 4.17 8.16 1.64 3.19 9.98 19.51
440V 7.05 7.05 2.76 16.86
220V 14.10 14.10 7.32 35.52
Option 2 380V 4.17 8.16 4.17 8.16 2.23 4.23 10.57 20.55
440V 7.05 7.05 3.66 17.76
Plenum Box 220V 14.10 14.10 1.80 30.00
Option 380V 4.17 8.16 4.17 8.16 0.45 1.04 8.79 17.36
440V 7.05 7.05 0.90 15.00
Maximum operation values Compressor 1 Compressor 2 Fan Motor Current
Fan Voltage CMO CMO CMO A
220V 19.80 19.80 5.18 44.78
STD 380V 11.46 11.46 2.99 25.91
440V 9.90 9.90 2.59 22.39
220V 19.80 19.80 6.91 46.51
Option 1 380V 11.46 11.46 3.99 26.91
440V 9.90 9.90 3.46 23.26
220V 19.80 19.80 9.15 48.75
Option 2 380V 11.46 11.46 5.28 28.20
440V 9.90 9.90 4.58 24.38
Plenum Box 220V 19.80 19.80 2.25 41.85
Option 380V 11.46 11.46 1.30 24.22
440V 9.90 9.90 1.13 20.93
Start-up values Compressor 1 Compressor 2 Fan Motor
Fan Voltage LRA LRA LRA
220V 128.00 128.00 30.92
STD 380V 74.11 74.11 17.85
440V 64.00 64.00 15.46
220V 128.00 128.00 48.36
Option 1 380V 74.11 74.11 27.92
440V 64.00 64.00 24.18
220V 128.00 128.00 60.45
Option 2 380V 74.11 74.11 34.90
440V 64.00 64.00 30.23
Plenum Box 220V 128.00 128.00 11.25
Option 380V 74.11 74.11 6.50
440V 64.00 64.00 5.63
Electrical
Data
To know which ventilation option should be used, consult the behavior of the
ventilation options.
CNO = Nominal operation current (A).
CMO = Maximum operation current.
LRA = Locked rotor amps.
STD Option - evaporator fan motor -1.5 CV.
Option 1 - evaporator fan motor -2 CV.
Option 2 - evaporator fan motor -3 CV.
Plenum box option - evaporator fan motor -0.5 CV.
Size the electrical wiring using the maximum operation currents.