GAT2A0C48 AIRFLOW PERFORMANCE TABLE
AIRFLOW PERFORMANCE
GAT2A0C48S41SA
EXTERNAL STATIC
(in w.g)
AIRFLOW (CFM)
Speed Taps - 230 VOLTS Speed Taps - 208 VOLTS
3 2 † 1 3 2 † 1
0 1904 1711 1541 1652 1455 1305
0.1 1881 1687 1529 1640 1450 1288
0.2 1844 1666 1511 1619 1425 1271
0.3 1806 1637 1485 1592 1410 1249
0.4 1766 1602 1454 1559 1381 1231
0.5 1716 1560 1420 1524 1351 1198
0.6 1659 1513 1380 1484 1321 1165
0.7 1594 1458 1333 1434 1283 1127
0.8 1525 1395 1277 1376 1229 1067
0.9 1442 1310 1194 1304 1149 N/A
1.0 1345 N/A N/A 1194 N/A N/A
NOTES:
1. Values are with wet coil and without filters.
2. Contact your particular filter manufacturer for pressure drop data.
3. Electric heater pressure drop is negligible and is included within the airflow data.
4. † Factory Setting
GAT2A0C48S41SA MINIMUM HEATER AIRFLOW CFM
Heater Minimum Air Speed Tap
With Heat Pump Without Heat Pump
BAYEAAC05BK1AA
BAYEAAC05LG1AA
Tap 1 Tap 1
BAYEAAC08BK1AA
BAYEAAC08LG1AA
Tap 1 Tap 1
BAYEAAC10BK1AA
BAYEAAC10LG1AA
Tap 1 Tap 1
BAYEABC15BK1AA Tap 1 Tap 1
BAYEABC20BK1AA Tap 1 Tap 1
BAYEACC25BK1AA Tap 3
Tap 2 1
1 Not qualified for 208 V
SEE AIR HANDLER NAMEPLATE FOR ADDITIONAL INFORMATION
Note: Heating and cooling
speeds are the same, factory
set at Speed Tap #2.