Trane GAT2A0C48S41SA Air Conditioner User Manual


 
Pub. No. 22-1857-03 11
Performance
Data
WIRING DATA
GAT2A0C48S41SA
Heater
Model
No.
No.
of
Circuits
240 VOLT 208 VOLT
Capacity
Heater
Amps
per
Circuit
Minimum
Circuit
Ampacity
Maximum
Overload
Protection
Capacity
Heater
Amps
per
Circuit
Minimum
Circuit
Ampacity
Maximum
Overload
Protection
kW BTUH kW BTUH
No Heater - - - 3.1** 4 15 - - 3.1** 4 15
BAYEAAC05++ 1 4.80 16400 20.0 29 30 3.60 12300 17.3 26 30
BAYEAAC08++ 1 7.68 26200 32.0 44 45 5.76 19700 27.7 38 40
BAYEAAC10++ 1 9.60 32800 40.0 54 60 7.20 24600 34.6 47 50
BAYEABC15++
circuit 1 9.60 32800 40.0 54 60 7.20 24600 34.6 47 50
circuit 2 4.80 16400 20.0 25 25 3.60 12300 17.3 22 25
BAYEABC20++
circuit 1 9.60 32800 40.0 54 60 7.20 24600 34.6 53 60
circuit 2 9.60 32800 40.0 50 50 7.20 24600 34.6 43 45
BAYEABC25++ 1
circuit 1 9.60 32800 40.0 54 60 7.20 24600 34.6 47 50
circuit 2 9.60 32800 40.0 50 50 7.20 24600 34.6 43 45
circuit 3 4.80 16400 20.0 25 25 3.60 12300 17.3 22 25
Note: ** Motor Amps
1 Not qualified for 208 V without Heat Pump