Trane GAT2A0C48S41SA Air Conditioner User Manual


 
12 Pub. No. 22-1857-03
Performance
Data
DISTANCE FROM BELLY BAND TO SHAFT FACE OF MOTOR FOR MINIMUM VIBRATION
WHEEL
BLOWER HOUSING
BELLY BAND
MOTOR
A
A is determined per chart
Wheel is centered in
Blower Housing
MODEL DIM "A"
GAT2A0B42S31SA 3
GAT2A0C48S41SA 2-13/16
GAT2A0C60S51SA 2-1/4
WIRING DATA
GAT2A0C60S51SA
Heater
Model
No.
No.
of
Circuits
240 VOLT 208 VOLT
Capacity
Heater
Amps
per
Circuit
Minimum
Circuit
Ampacity
Maximum
Overload
Protection
Capacity
Heater
Amps
per
Circuit
Minimum
Circuit
Ampacity
Maximum
Overload
Protection
kW BTUH kW BTUH
No Heater - - - 7.6** 10 15 - - 7.6** 10 15
BAYEAAC05++ 1 4.80 16400 20.0 35 35 3.60 12300 17.3 31 35
BAYEAAC08++ 1 7.68 26200 32.0 50 50 5.76 19700 27.7 44 45
BAYEAAC10++ 1 9.60 32800 40.0 60 60 7.20 24600 34.6 53 60
BAYEABC15++
circuit 1 9.60 32800 40.0 60 60 7.20 24600 34.6 53 60
circuit 2 4.80 16400 20.0 25 25 3.60 12300 17.3 22 25
BAYEABC20++
circuit 1 9.60 32800 40.0 60 60 7.20 24600 34.6 53 60
circuit 2 9.60 32800 40.0 50 50 7.20 24600 34.6 43 45
BAYEABC25++
circuit 1 9.60 32800 40.0 60 60 7.20 24600 34.6 53 60
circuit 2 9.60 32800 40.0 50 50 7.20 24600 34.6 43 45
circuit 3 4.80 16400 20.0 25 25 3.60 12300 17.3 22 25
Note: ** Motor Amps