Toshiba RAV-SP420CT-UL Air Conditioner User Manual


 
–25–
Under Ceiling Type
Installation Manual
Toshiba
Procedure 6
If there is other indoor unit to be changed, repeat
procedure
2 to 5 to change the setup.
When the above setup has finished, push to
select the indoor UNIT No. before change of setup,
specify CODE No. [12], [13], [14] in order with temp.
setup / buttons, and then check the changed
contents.
Address change check Before change:
[3-3-1] After change: [2-2-2]
Pushing button clears the contents of which setup
was changed.
(In this case, procedure from
2 is repeated.)
Procedure 7
After check of the changed contents, push button.
(Setup is determined.) When pushing
button, the
display disappears and the status becomes the usual
stop status. (When pushing
button the operation
from the remote control is not accepted for approx.
1 minute.)
* If the operation from the remote control is not
accepted even 1 minute or more passed after
pushing
button, it is considered that the address
setup is incorrect.
In this case, the automatic address must be again
set up.
Therefore repeat procedure of the setup change
from the Procedure
1.
To recognize the position of the
corresponding indoor unit though the
indoor UNIT No. is known
Check the position during operation stop.
(Be sure to stop operation of the set.)
Procedure 1
Push simultaneously + buttons for 4 seconds
or more.
After a while, the display part flashes and the display
appears as shown below.
In this time, the position can be checked because fan
and louver of the indoor unit operate.
For the group control, the indoor UNIT No. is
displayed as [ ] and fans and louvers of all the
indoor units in the group control operate.
Check the displayed CODE No. is [01].
When the CODE No. is other than [01], push
button to erase the display and repeat procedure
from the first step.
(After pushing
button, operation of the remote
control is not accepted for approx. 1 minute.)
Procedure 2
In the group control, every pushing button, the
indoor UNIT No. in the group control is displayed in
order.
In this time, the position of the indoor unit can be
confirmed because only fan of the selected indoor unit
operate.
(For a group control, No. of the firstly displayed indoor
unit becomes the header unit.)
Procedure 3
After confirmation, push button to return the mode
to the usual mode.
When pushing
button, the display disappears and
the status becomes the usual stop status.
(When pushing
button the operation from the
remote control is not accepted for approx. 1 minute.)
Indoor UNIT No. before setup change is displayed.
2
1,3
1
(* Display changes according to
the model No. of indoor unit.)
25-EN
+00EH99864801_00Ta.book Page 25 Tuesday, November 24, 2009 5:40 PM