– 14 –
<Twin type>
Indoor unit 1 RAV-SM402MUT-E
Model Indoor unit 2 RAV-SM402MUT-E
Outdoor unit RAV-SP804AT(Z)(ZG)-E
Cooling capacity (kW) 7.1
Heating capacity (kW) 8.0
Indoor unit
Power supply 1 phase 230V (220 – 240V) 50Hz
Running current (A) 10.36 – 9.49
Power consumption (kW) 2.21
Cooling Power factor (%) 97
EER 3.21
Electrical
Energy efficiency class ∗ A
characteristics
Running current (A) 10.12 – 9.28
Power consumption (kW) 2.16
Heating Power factor (%) 97
COP 3.70
Energy efficiency class ∗ A
Fan Turbo fan
Fan unit Standard air flow H/M/L (m³/min.) 11.0 / 9.2 / 7.8
Motor (W) 60
Sound pressure level H/M/L (dB•A) 40 / 36 / 31
Sound power level H/M/L (dB•A) 55 / 51 / 46
Outdoor unit
Power supply 1 phase 230V (220 – 240V) 50Hz
Standard length (m) 7.5
Min. length (m) 5
Refrigerant
Max. total length (m) 50
Refrigerant charging amount 40g/m
pipe
(Charge-less up to 30m) (31m to 50m)
Height
Outdoor lower (m) 30
difference
Outdoor higher (m) 30
Fan Propeller fan
Fan unit Standard air flow volume (m³/min.) 50
Motor (W) 63
Gas side
Main (mm) 15.9
Connecting
Sub (mm) 12.7
pipe
Liquid side
Main (mm) 9.5
Sub (mm) 6.4
Sound pressure level Cooling/Heating (dB•A) 48 / 49
Sound power level Cooling/Heating (dB•A) 64 / 65
∗ : IEC standard