– 114 –
Function selection item No. (DN) list
DN
01
02
03
06
0F
10
11
12
13
14
1E
28
2A
2b
2E
31
32
40
5d
60
C2
D0
D1
Item
Filter sign lighting time
Filter stain level
Central control address
Heating suction temp. shift
Cooling-only
Ty p e
Indoor unit capacity
Line address
Indoor unit address
Group address
In automatic cooling/heating, temp.
width of cool → heat, heat →
cool mode selection control point
Automatic reset of power failure
Selection of option / error input
(CN70)
Selection of thermostat output
(T10 )
Selection of HA (T10) terminal
Fan (Single operation)
Sensor selection
Humidifier control
(+Drain pump control)
(This function is not provided.)
External static pressure
Timer setting
(Wired remote controller)
Current demand X% to outdoor unit
Existence of remote controller save
function
Existence of 8°C heating operation
function
Contents
0000: None 0001: 150H
0002: 2500H 0003: 5000H
0004: 10000H 0005: Clogging sensor used
0000: Standard
0001: Heavy stain (Half of standard time)
0001: No.1 unit to 0064: No.64 unit
0099: Undecided
0000: No shift 0001:+1°C
0002: +2°C to 0010:+10°C
(Up to +6 is recommended.)
0000: Heat pump
0001: Cooling only (No display for [AUTO] [HEAT] )
0000: (1-way air discharge cassette)
0001: (4-way air discharge cassette) to 0037
0000: Undecided 0001 to 0034
0001: No.1 unit to 0030: No.30 unit
0001: No.1 unit to 0064: No.64 unit
0000: Individual 0001: Master unit in group
0002: Follower unit in group
0000: 0 deg to 0010: 10 deg
(Cool/heat are reversed with ± (Data value) /
2 against the set temperature)
0000: None 0001: Provided
0000: Filter input
0001: Alarm input (Air cleaner, etc.)
0002: Humidifier input
0000: Indoor thermostat ON
0001: ON receiving output of outdoor compressor
0000: Normal (JEMA)
0001: Card input (Forgotten to be off)
0002: Fire alarm input
0000: Impossible 0001: Possible
0000: Body TA sensor
0001: Remote controller sensor
0000: No control
0001: Humidifier + Vaporizing type (Pump ON)
0002: Humidifier + Supersonic type
(Pump ON when specified time elapsed)
0003: Humidifier + Natural drain type (Pump OFF)
0000: Standard (At shipment) (10 Pa)
0001: High static pressure 1 (20 Pa)
0003: High static pressure 2 (35 Pa)
0006: High static pressure 3 (50 Pa)
0000: Operable
0001: Operation prohibited
0050: 50% to 0100: 100%
0000: Invalid (Impossible)
0001: Valid (Possible)
0000: Invalid (Impossible)
0001: Valid (Possible)
At shipment from factory
According to type
0000: Standard
0099: Undecided
0002: +2°C
(Floor type 0000: 0°C)
0000: Heat pump
According to model type
According to capacity type
0099: Undecided
0099: Undecided
0099: Undecided
0003: 3 deg (Ts±1.5)
0000: None
0002: Humidifier
0000: Thermostat ON
0000: Normal (HA terminal)
0000: Impossible
0000: Body sensor
0003: Humidifier ON
Pump OFF
0000: Standard
0000: Operable
0075: 75%
0001: Valid (Possible)
0001: Invalid (Impossible)