Toshiba RAV-SP240CT-UL Air Conditioner User Manual


 
–22–
Under Ceiling Type
Installation Manual
EN
Toshiba
Procedure 5
Push button. In this time, if the display changes
from flashing to lighting, the setup completes.
To change the setup of an indoor unit other than the
selected one, start operation from Procedure
2.
To change the setup of another setup in the selected
indoor unit, start operation from Procedure
3.
Pushing button clears the set up contents which
have been already set. In this case, retry from
Procedure
2.
Procedure 6
When settings have been completed, push button
to determine the settings.
When button is pushed, “SETTING” flashes and
then the display content disappears and the air
conditioner enters the normal stop mode.
(While “SETTING” is flashing, no operation of the
remote control is accepted.)
Installation to high ceiling
When the height of the ceiling to be installed exceeds
3.5 m (11’6”), adjustment of fan speed is necessary.
Set up the high ceiling.
Set according to the basic operation procedure
(
1 2 3 4 5 6).
Item code in Procedure specifies [5d].
Select [SET DATA] in Procedure from “List of
installable ceiling height” in this Manual.
For the item code in Procedure
3, specify [5d].
For the SET DATA in Procedure
4, select the setup
data of static pressure to be set up from the table on
the right.
(Exchange by wired remote control)
Using wireless remote control
Change the high ceiling setting with the DIP switch on
the P.C. board of the signal receiving part.
Refer to the installation manual of the wireless remote
controller kit for the details.
High ceiling setting can be changed by arranging the
jumper block on the indoor unit micro computer P.C.
board as shown in the table below as well.
* However, once the setting is changed, it is
necessary to reset the setting back to 0000 that
placing the jumper block back to the factory default
position and rewriting the setting data back to 0000
with wired remote control (sold separately). (The
setting can be changed to 0001, 0003 and 0006
without resetting.)
Select by exchange of jumper block on indoor
microcomputer P.C. board.
SET DATA
0000
Standard
(Factory default)
11’6” (3.5 m) or less
0001 High static pressure 1
more than 11’6” (3.5 m)
up to 13’1” (4.0 m)
SET DATA Note
0000
Standard filter
(Factory default)
0001 High static pressure 1
jumper block
position
Short Open
Jumper block position
(CN112, CN111, CN110 from the left)
22-EN
+00EH99864801_00Ta.book Page 22 Tuesday, November 24, 2009 5:40 PM