– 96 –
(Example of 2-lines cabling)
(Real line: Cabling, Broken line: Refrigerant pipe)
For the above example, perform setting by
connecting singly the wired remote controller
without remote controller inter-unit cable.
Group address
Individual : 0000
Master unit : 0001
Sub unit : 0002
In case of group control
Outdoor
Indoor
A B
A B
1 2 3
Indoor
A B
1 2 3
Indoor
A B
1 2 3
Indoor
A B
1 2 3
1 23
Outdoor
1 2 3
Remote controller
Line address → 1
Indoor unit address → 1
Group address → 1
1
2
2
2
1
2
2
2
2
<Operation procedure>
1 2 3 4 5 6 7 8 9 10 11 END
1
3, 6, 9
END 11
2, 5, 8
4, 7, 10
S
E
T
TIM
E
TIMER
S
E
T
TE
ST
FIL
TER
L
L
RE
S
E
T
TEMP
.
CL
FA
N
SA
VE
A
A
SWING
/
FI
X
VEN
T
M
O
D
E
ON
/
OF
F
U
NI
T
LOUVER
T
10-4. Address Setup (Manual setting from remote controller)
1 Push
SET
+
CL
+
TES
T
buttons simultaneously
for 4 seconds or more.
2 (
←←
←←
← Line address)
Using the temperature setup
/ buttons,
set
12 to the CODE No.
3 Using timer time / buttons, set the line address.
4 Push
SET
button. (OK when display goes on.)
5 (
←←
←←
← Indoor unit address)
Using the temperature setup
/ buttons, set 13 to the CODE No.
6 Using timer time / buttons, set 1 to the line address.
7 Push
SET
button. (OK when display goes on.)
8 (
←←
←←
← Group address)
Using the temperature setup
/ buttons, set 14 to the CODE No.
9 Using timer time / buttons, set 0000 to Individual, 0001 to Master unit, and 0002 to sub unit.
10 Push
SET
button. (OK when display goes on.)
11 Push
TES
T
button.
Setup completes. (The status returns to the usual stop status.)
In case that addresses of the indoor units will be
determined prior to piping work after cabling work
• Set an indoor unit per a remote controller.
• Turn on power supply.