Toshiba RAV-SP1404AT8ZG-TR Air Conditioner User Manual


 
– 80 –
Resistance (kΩ) (50˚C or lower)
Resistance (kΩ) (50˚C or higher)
0
0
50
100
150
200
0
5
10
15
20
10 20 30 40 50 60 70 80 90 100
Temperature (˚C)
Resistance (kΩ)
0
0
10
20
30
40
Output voltage (V)
10 20 30 40 50 60 70 80 90 100
Temperature (˚C)
Temperature sensor Temperature – Resistance value characteristic table
TA, TC, TCJ, TE, TS, TO sensors
Representative value
TD, TL sensors
Representative value
TA, TC, TCJ, TE, TS, TO sensors
TD, TL sensors
Temperature
(°C)
0
10
20
25
30
40
50
60
70
80
90
100
Resistance value (k
ΩΩ
ΩΩ
Ω)
(Minimum value) (Standard value) (Maximum value)
32.33 33.80 35.30
19.63 20.35 21.09
12.23 12.59 12.95
9.75 10.00 10.25
7.764 7.990 8.218
5.013 5.192 5.375
3.312 3.451 3.594
2.236 2.343 2.454
1.540 1.623 1.709
1.082 1.146 1.213
0.7740 0.8237 0.8761
0.5634 0.6023 0.6434
Temperature
(°C)
0
10
20
25
30
40
50
60
70
80
90
100
Resistance value (k
ΩΩ
ΩΩ
Ω)
(Minimum value) (Standard value) (Maximum value)
150.5 161.3 172.7
92.76 99.05 105.6
58.61 62.36 66.26
47.01 49.93 52.97
37.93 40.22 42.59
25.12 26.55 28.03
17.00 17.92 18.86
11.74 12.34 12.95
8.269 8.668 9.074
5.925 6.195 6.470
4.321 4.507 4.696
3.205 3.336 3.468
As TH sensor (Outdoor unit heat sink temp. sensor) is incorporated in the outdoor control P.C. board, the
resistance value cannot be measured.