Toshiba RAV-SM800XT-E Air Conditioner User Manual


 
– 58 –
<Inspection procedure>
-Cooling and heating model-
Is it possible to start
unit by remote control?
Is it possible to detect
DC 15 60 V between
2 and 3 on terminal block?
Is crossover cable normal?
Is it possible to detect
AC 12 V on secondary side
(CN06) of transformer?
YES
YES
YES
YES
YES
Turn on power supply.
Does OPERATION
lamp blink?
YES
NO
NO
NO
Refer to 9-9 Troubleshooting
for Remote Control .
Connect crossover
cable properly.
NO
NO
NO
Replace outdoor
P.C. board.
Replace outdoor
P.C. board.
Replace outdoor
transformer.
NO
Check TA and TC sensors
or refer to 01 04 in Table 9-4-1.
Is it possible to detect
DC 5 V at Q60 and 12 V at Q50?
YES
Replace MG switch.
NO
Does MG switch operate?
(Next Page)
Is it possible to detect
AC 220 240 V at CN11?
Are TD and TE sensors normal?
(TD=17.9 k at 50°C)
(TE=10 k at 25°C)
YES
Replace sensors.
NO
Refer to item Power
can not be turned on .
All lamps on
indoor unit normal?
YES
NO
Refer to item 9-8-3 How to
check outdoor P.C. board.