Toshiba RAV-SM800XT-E Air Conditioner User Manual


 
– 51 –
10-3. Troubleshooting for Each Check Code
[1A error]
Are connections of CN301 and
CN300 of CDB correct?
(CDB error)
NO
NO
NO
YES
YES
YES
YES
Does the fan rotate without trouble
when handling the fan with hands under condition
of removing CN301 and CN300 from CDB?
The status that the resistance values
between leads below are 50 to 80
for 40 W motor (ICF-140-43) and 25 to 55
for 60 W motor (ICF-140-63-1) is normal.
Between 1 (Red lead) and 2 (White lead)
Between 2 (White lead) and 3 (Black lead)
Between 3 (Black lead) and 1 (Red lead)
of motor winding of connector (CN301)
Normal fan motor
Defective fan motor
The status that there is
5k to 20kresistance values between
1 (Yellow lead) and 4 (Pink lead)
of motor position detection of connector
(CN300, CN302) is normal.
CN301
CN300
For RAV-SM560AT-E, CN300 changes to
CN301, and CN301 to CN300, respectively.
NOTE :
However, GND circuit error inside of the motor is rarely detected even if the above check is carried out. When
the circuit does not become normal even if P.C. board has been replaced, replace outdoor fan motor.
RAV-SM560AT-E RAV-SM800AT-E
Objective P.C. board Control P.C. board CDB P.C. board
Fan motor winding CN300 CN301
Motor position detection CN301 CN300