1. SPECIFICATIONS
1-1. Indoor Unit
Model name RAV-SM560XT-E RAV-SM800XT-E
Cooling Heating Average Cooling Heating Average
Standard capacity (Note 1) kW 5.0 5.6 6.7 8.0
(1.5 – 5.6) (1.5 – 6.3) (2.2 – 8.0) (2.2 – 9.0)
Heating low temp. capacity (Note 1) (kW) 4.9 5.8
Energy consumption effect ratio (Cooling) 2.67 [D] 3.29 [C] 2.98 2.46 [E] 3.00 [D] 2.73
Power supply 1 phase 220 – 240V 50Hz
Running current (A) 8.95 – 8.20 8.13 – 7.46
13.15 – 12.06 12.91 – 11.84
Power consumption (kW) 1.87 1.7 2.72 2.67
(Low temp.) (kW) 2.18 2.29
Power factor (%) 95 95 94 94
Main unit Pure white
Appearance
Ceiling panel
Model –––
(Sold separately)
Panel color –––
Height (mm) 633
Main unit Width (mm) 1093
Outer
Depth (mm) 208
dimension
Height (mm) –––
Width (mm) –––
Depth (mm) –––
Total weight
Main unit (kg) 23
Ceiling panel –––
Heat exchanger Finned tube
Fan Multi blade fan
Fan unit Standard air flow High (Mid./Low) (m
3
/h) 800 (680/580) 900(750/550)
Motor (W) 50
Air filter Washable filter
Controller (Sold separately) Wireless remote control
Gas side (mm) 12.7 (1/2”) 15.9 (5/8”)
Dimensions pipe Liquid side (mm) 6.4 (1/4”) 9.5 (3/8”)
Drain port (Nominal dia.) 25 (Polyvinyl chloride tube)
Sound level High (Mid./Low) (Note 2) (dB•A) 43 39 36 46 42 37
Electrical
characteristics
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8616
based on the reference piping length 7.5 m with 0 meter height.
Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Normally, the values
measured in the actual operating environment become larger than the indicated values due to the effects of
external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
Ceiling panel
(Sold separately)