8. REPLACEMENT OF SERVICE P.C. BOARD
8-1. Indoort Unit
<Note: when replacing the P.C. board for indoor unit servicing>
The nonvolatile memory (hereafter called EEPROM, IC503) on the indoor unit P.C. board before replacement
includes the model specific type information and capacity codes as the factory-set value and the important setting
data which have been automatically or manually set when the indoor unit is installed, such as system/indoor/group
addresses, high ceiling select setting, etc.
When replacing the P.C. board for indoor unit servicing, follow the procedures below.
After replacement completes, confirm whether the settings are correct by checking the indoor unit No., Group
master unit / sub unit settings and perform the cooling cycle confirmation through the trial operation.
<Replacement procedures>
CASE 1
Before replacement, the indoor unit can be turned on and the setting data can be read out by wired
remote control operation.
EEPROM data read out [1]
ò
Replacement of P.C. board for Indoor unit servicing and power on [2]
ò
Writing the read out EEPROM data [3]
ò
Power reset
(for all indoor units connected to the remote control when the group operation control is performed.)
CASE 2
Before replacement, the indoor unit cannot be turned on or the wired remote controller operation is
impossible due to trouble of the power supply circuit to the remote controller. (Defective P.C. board)
Replacement of EEPROM
Remove EEPROM installed on the P.C. board before replacement
and then replace it with EEPROM of the service P.C. board.
ò
Replacement & power ON for service P.C. board [2]
ò
Read-out of EEPROM data [1]
If reading-out is impossible, proceed to CASE 3.
ò
Replacement of EEPROM
Replace EEPROM again. (Set the original EEPROM to the service P.C. board.)
ò
Replacement & power ON for service P.C. board [2]
ò
Writing-in of the read-out EEPROM data [3]
Power reset
(for all indoor units connected to the remote controller when the group operation control is performed.)
CASE 3
The EEPROM before replacement is defective and the setting data cannot be read out.
Replacement & power ON for service P.C. board [2]
ò
Writing the setting data to EEPROM, such as high ceiling installation setting
and optional connection setting, etc., based on the customer information. [3]
ò
Power reset
(for all indoor units connected to the remote control when the group operation control is performed.)