Toshiba RAV-SM1603ATZ-E Air Conditioner User Manual


 
– 57 –
A
B
L
N
M
(˚C)Tc
Tcj
No.
9
10
11
Item
High-temp.
release control
Drain pump
control
(Sold separately)
After-heat
elimination
Outline of specifications
1) The heating operation is performed as follows based on the
detected temperature of Tc sensor or Tcj sensor.
When [M] zone is detected, the commanded frequency is
decreased from the real operation frequency. After then
the commanded frequency changes every 30 seconds
while operation is performed in [M] zone.
In [N] zone, the commanded frequency is held.
When [L] zone is detected, the commanded frequency is
returned to the original value by approx. 6Hz every
60 seconds.
Setup at shipment
Control temp. (°C)
AB
56 (54) 52 (52)
NOTE:
When the operation has started or when Tc or Tcj < 30°C at
start of the operation or after operation start, temperature is
controlled between values in parentheses of A and B.
1) In cooling operation, the drain pump is usually operated.
2) If the float switch works while drain pump drives, the
compressor stops, the drain pump continues the operation,
and a check code is output.
3) If the float switch works while drain pump stops, the
compressor stops and the drain pump operates. If the float
switch keeps operating for approx. 4 minutes, a check code
is output.
When heating operation stops, in some cases, the indoor fan
operates with (L) for approx. 30 seconds.
Remarks
However this control is
ignored in case of the
follower unit of the twin.
Same status as that
when “thermostat-OFF”
(status that the air
conditioner enters in the
room temp. monitor
mode when the
temperature reached
the setup temperature
on the remote controller)
Check code [P10]
12 Frequency fixed
operation
(Test run)
<In case of wired remote controller>
1) When pushing [CHK] button for 4 seconds or more, [TEST]
is displayed on the display screen and the mode enters in
Test run mode.
2) Push [ON/OFF] button.
3) Using [MODE] button, set the mode to [COOL] or [HEAT].
Do not use other mode than [COOL]/[HEAT] mode.
During test run operation, the temperature cannot be
adjusted.
An error is detected as usual.
A frequency fixed operation is performed.
4)
After the test run, push [ON/OFF] button to stop the operation.
(Display in the display part is same as the procedure in Item 1.)
5) Push [CHK] button to clear the test run mode.
([TEST] display in the display part disappears and the
status returns to the normal stop status.)