Toshiba RAV-SM1406BT-E Air Conditioner User Manual


 
– 66 –
Item No. (DN) table (Selection of function)
DN
01
02
03
06
0F
10
11
12
13
14
19
1E
28
2A
2b
2E
30
31
32
33
40
5d
Item
Filter sign lighting time}
Dirty state of filter
Central control address
Heating suction temp shift
Cooling only
Type
Indoor unit capacity
Line address
Indoor unit address
Group address
Louver type
(Air direction adjustment)
None for concealed duct
Temp difference of
automatic cooling/heating
mode selection COOL
HEAT, HEAT COOL
Auto restart after power
failure
Option
Thermo output selection
(T10
e
)
Option
Option
Option
Sensor selection
Temperature indication
Option
High ceiling selection
(External static pressure
selection)
Description
0000 :None
0002 :2500H (4-Way/Duct/Ceiling Type)
0000 :Standard 0001 : High degree of dirt
(Half of standard time)
0001 :No.1 unit to 0064 : No.64 unit
0099 :Unfixed
0000 :No shift 0001 : +1°C
0002 :+2°C to 0010 : –10°C
(Up to recommendation + 6)
0000 :Heat pump 0001 : Cooling only
(No display of [AUTO] [HEAT])
0004 :Concealed duct type 0007 : Ceiling type
0014 :Compact 4-way cassette type
0000 :Unfixed 0006 : 40 type
0007 :45 type 0009 : 56 type
0012 : 80 type 0015 : 110 type
0017 : 140 type 0018 : 160 type
0001 :No.1 unit to 0030 : No.30 unit
0001 :No.1 unit to 0064 : No.64 unit
0000 :Individual 0001 : Master of group
0002 :Follower of group
0000 :No louver 0001 : Swing only
0002 :1-way 0003 : 2-way
0004 :4-way
0000 :0 deg to 0010 : 10 deg
(For setup temperature, reversal of COOL/HEAT by ± (Data value)/2)
0000 :None 0001 : Auto restart
0000 :Indoor thermo ON
0001 :Output of outdoor comp-ON receiving
0000 :Body TA sensor0001 : Remote controller sensor
0000 :°C (celsius) 0001 : °F (Fahrenheit)
<Concealed Duct type>
At shipment
0002 :2500H
0000 : Standard
0099 : Unfixed
0002 : +2°C
0000 : Heat pump
According to model type
According to capacity type
0099 :Unfixed
0099 :Unfixed
0099 :Unfixed
According to model type
0003 :3 deg (Ts±1.5)
0000 :None
0002 :Default
0000: Thermo. ON
0000 :Default
0000 :Default
0000 :Default
0000 :Body sensor
0000 :°C
0003 :Default
According to capacity type
The list above is when SW501-1 and SW501-2 is OFF.
Set data
External static
pressure
0000 0001 0002 0003 0004 0005
40 Pa
To 3HP
(Factory
default)
4 to 6HP
(Factory
default)
30 Pa 65 Pa 50 Pa 80 Pa 100 Pa
0006
120 Pa
——