Toshiba RAV-SM1101AT-E Air Conditioner User Manual


 
7
RAV-SM561AT-E, RAV-SM801AT-E
500
Strong
wind
Strong
wind
2) Supposing the wind direction during the
operation season of the air conditioner,
install the unit so that the discharge port is
set at right angle to the wind direction.
4. Installation in the following places may result in
some troubles. Do not install the unit in such
places below.
A place full of machine oil.
A place full of sulfuric gas.
A place where high-frequency radio waves
are likely to be generated as from audio
equipment, welders, and medical equipment.
150
or more
300
or more
300
or more
300
or more
200 or more
The height of the obstacle should be lower
than the height of the outdoor unit.
1000
or more
Necessary Space for Installation
Obstacle at rear side
<Upper side is free>
1. Single unit installation
150
or more
150
or more
300
or more
200
or more
The height of the
obstacle should be
lower than the height
of the outdoor unit.
500
or more
150
or more
500
or more
2. Obstacles at both right and left sides.
3. Serial installation of two or more units
<Obstacle also at the upper side>
Obstacle at front side
<Upper side is free>
1. Single unit installation
2. Serial installation of two or more units
Installation Place
A place which provides a specified space around
the outdoor unit.
A place where the operation noise and discharged
air are not given to your neighbors.
A place that is not exposed to a strong wind.
A place that does not block a passage.
When the outdoor unit is installed in an elevated
position, be sure to secure its feet.
There must be sufficient space for carrying in the
unit.
A place where the drain water does not make any
problem.
CAUTION
1. Install the outdoor unit at a place where dis-
charge air is not blocked.
2. When an outdoor unit is installed in a place that
is always exposed to a strong wind like a coast
or on a high story of a building, secure a
normal fan operation by using a duct or a wind
shield.
3. When installing the outdoor unit in a place that
is constantly exposed to a strong wind such as
the upper stairs or rooftop of a building, apply
the windproof measures referring to the follow-
ing examples.
1) Install the unit so that its
discharge port faces to
the wall of the building.
Keep a distance 500 mm
or more between the unit
and the wall surface.