Toshiba RAV-SM1101AT-E Air Conditioner User Manual


 
23
RAV-SM1101AT-E, RAV-SM1401AT-E
Tightening of Connecting Part
(Unit: Nm)
Externally
threaded side
Internally
threaded side
Fix with spanner.
Tighten with torque wrench.
Half union or packed valve Flare nut
Flare at
indoor unit side
Flare at
outdoor unit side
Align the centers of the connecting pipes and
tighten the flare nut strong as far as possible with
your fingers.
Then fix the nut with a spanner and tighten it with
torque wrench as shown in the figure.
Cover
Cap
Piping valve
Tightened
Flare nut
Loosened
As shown in the figure, be sure to use a double
spanner to loosen or tighten the flare nut of the
valve at gas side. If using a single spanner, the nut
cannot be tightened with necessary tightening
torque.
On the contrary, use a single spanner to loosen or
tighten the flare nut of the valve at liquid side.
Cover
NO GOOD
Valve at gas side
Pressure of R410A is higher than that of R22
(Approx. 1.6 times). Therefore, using a torque
wrench, tighten the flare pipe connecting sections
which connect the indoor/outdoor units at the
specified tightening torque. Incomplete connections
may cause not only a gas leak, but also a trouble of
the refrigeration cycle.
Do not apply refrigerating machine oil to
the flared surface.
REQUIREMENT
1. Do not put the spanner on the cap.
The valve may be broken.
2. If applying excessive torque, the nut may be
broken according to some installation condi-
tions.
After the installation work, be sure to check gas leak
of connecting part of the pipes with nitrogen.
Outer dia. of copper pipe
6.4 mm (diam.)
9.5 mm (diam.)
12.7 mm (diam.)
15.9 mm (diam.)
Tightening torque
14 to 18 (1.4 to 1.8 kgfm)
33 to 42 (3.3 to 4.2 kgfm)
50 to 62 (5.0 to 6.2 kgfm)
68 to 82 (6.8 to 8.2 kgfm)