– 117 –
RAV-SM561CT-E, RAV-SM801CT-E, RAV-SM1101CT-E, RAV-SM1401CT-E
Accessory parts and Parts to be procured locally
r Accessory parts
<Separate sold parts>
Part name
Standard wired
remote controller
Q’ty
1
Shape Usage
Model
RBC-AMT21E
Part name
Owner’s Manual
Installation Manual
Installation pattern
Thermal insulation
pipe
Washer
Hose band
Q’ty
1
1
1
2
4
2
Shape
—
This manual
—
M10 × Ø25
Usage
—
—
Drawing-out port of
hanging bolt pipe
For thermal insulation of
pipe connecting section
For holding down unit
For connecting drain
pipe
Part name
Drain hose
Bushing
Thermal insulator
Thermal insulator
of top plate
Banding band
Q’ty
1
1
1
1
2
Shape
Usage
For connecting drain pipe
For protection of edge at
power taking-in port
For thermal insulation of drain
hose (10t × 200 × 200)
For upper pipe hole of indoor
unit (6t × 130 × 160)
For prevention of open of
drain hose thermal insulator
r Parts to be procured locally
Connecting pipe (Liquid side)
(6.4mm (diam.), Nominal (diam.) 1/4” thick 0.8mm)
RAV-SM561CT-E
(9.52mm (diam.), Nominal (diam.) 3/8” thick 0.8mm)
RAV-SM801CT-E, RAV-SM1101CT-E, RAV-SM1401CT-E
Connecting pipe (Gas side)
(12.7mm (diam.), Nominal (diam.) 1/2” thick 0.8mm)
RAV-SM561CT-E
(15.9mm (diam.), Nominal (diam.) 5/8” thick 1.0mm)
RAV-SM801CT-E, RAV-SM1101CT-E, RAV-SM1401CT-E
Power supply cord
2.5mm² (H07RN-F or 245IEC66) (20m or less)
3.5mm² (AWG-12) (50m or less)
Connecting cable (indoor and outdoor cable)
H07RN-F or 245IEC66 (1.5mm² or more)
Thermal insulation for refrigerant pipe
(10mm or more, thermal insulating foam polyethylene)
Thermal insulation for drain pipe
(10mm or more, foam polyethylene)
Drain pipe (Outer 26mm (diam.)) (VP20)
Tapes