Toshiba HWS-802XWHT6-E Heat Pump User Manual


 
110
Toshiba
4. Auto Curve Setting
FC code setting can make flexible Auto-Curve settings.
<Preparation>
1 Press the TEST and SET and SELECT
buttons at the same time for 4 seconds or longer.
(See display )
(Make sure that no operation is in progress.)
2 Specify an item code (FC) from among 29 to 2F with the
TEMP. button for temperature setting.
3 Set data with the TIME button for timer setting.
4 Press the SET button. (If lights, the status is
confirmed)
5 Repeat 2 through 4 for each item.
6 Pressing the TEST button moves the unit to the normal
stop state.
Auto-Curve temperature shift
Without Auto-Curve individually set, the set temperature can be
shifted in the range of ±5k of the current setting. (The set temperature
is valid only when Auto operation is in progress.)
1 Press the AUTO TEMP button for 4 seconds or
longer. (See display )
(The remote controller FC setting screen appears.)
2 Set a temperature shift range with the TEMP.
button for temperature setting. (-5k to 5k)
3 Press the SET button. (If lights, the status is
confirmed)
4 Pressing the TEST button moves the unit to the normal
stop state.
FC Item Details Fist shipment
29 Outside air temperature T1 temperature -0015: -15°C - 0000: 0°C -0010: -10°C
2B Outside air temperature T3 temperature 0000: 0°C - 0015: 15°C 0010: 10°C
2C Set temperature A with outside air temperature of -20°C 0020: 20°C - 0055: 55°C 0040: 40°C
2D Set temperature B with outside air temperature of T1 0020: 20°C - 0055: 55°C 0035: 35°C
2E Set temperature C with outside air temperature of 0°C 0020: 20°C - 0055: 55°C 0030: 30°C
2F Set temperature D with outside air temperature of T3 0020: 20°C - 0055: 55°C 0025: 25°C
30 Set temperature E with outside air temperature of 20°C 0020: 20°C - 0055: 55°C 0020: 20°C
31 Zone2 ratio with Zone1 as Auto 0000: 0% - 0100: 100% 0080: 80%
2
3
64
1
E(20)
-20 T1
(-10)
0T3
(+10)
20
Outside
air temperature (TO)
D(25)
C(30)
B(35)
A(40)
TSC-F
Set temperature ( )
Auto-Curve
Temperature shift
Default Setting
2
43
1
+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 110 Monday, October 5, 2009 2:09 PM