Large Dehumidifying Dryers Operation 38
on the relay screen. Press ALARM RESET to deactivate the alarm until the next dew
point fault occurs.
15. Use the right arrow key to display the REGEN SET screen (Screen 1). Use the up &
down arrow keys to select the parameter to change. Use the + & - keys to change the
parameter value. Press the OK key to accept and store the changed values. Press
ESC to cancel changes.
Screen 1.
16. Use the right arrow key to display the Material Miser screen. Use the + key to enable/
disable this feature. See Screens 2 & 3.
Screen 2.
Screen 3.
17. Use the right arrow key to display the Closed Loop Regen screen. Use the + key to
enable / disable this feature. See Screens 4 & 5.
Screen 4.
Screen 5.
CL REGEN ON
+ TO DISABLE
CL IS :
NOT ACTIVE
CLOSED LOOP
REGEN OFF
PRESS + TO
ENABLE
MTL MISER ON
+ TO DISABLE
MM IS :
NOT ACTIVE
MATERIAL
MISER OFF
PRESS + TO
ENABLE
REGEN
SET
HEAT 45
COOL 20