State Industries SBD71 120 Water Heater User Manual


 
SBD TANK TYPE HEATERS
SERVICE HANDBOOK
Technical Training Department
Ashland City, TN ©2003
30
TROUBLESHOOTING THE EFFIKAL DAMPER (continued)
Condition:
Thermostat closed, damper is open fully
STEP 10A TEST FOR 24VAC BETWEEN BLACK AND YELLOW
NEHT FI
11 petS ot eunitnoc tcerroc si sihT tneserp si CAV42
24VAC is not present See Step 9B.
Check the harness plug connecting.
Check that cam on shaft rotates with
shaft.
Replace the damper board.
Ensure that cam is secure against end
switch.
Condition:
Damper rotates continuously
STEP 10B ADJUST END SWITCH TO CAM CONTACT
NEHT FI
Damper stops in proper position 24 VAC should be open on a call for heat
and close during standby/
Damper does not stop in proper position Replace damper assembly.