PREPARING TO PROGRAM THE KEYPAD
To program the SK-1123-SQ, first determine the following information:
1. The master code
--
Allows the system administrator to program or operate the keypad.
2. The user code or codes
--
Allows users to use the keypad's functions.
3. Configuration of the relays and outputs
--
For relay output #1 and relay output #2, determine whether
the output should operate from 1 to 999 seconds and then turn OFF (momentary mode), or turn ON/
OFF via the code (shunt mode).
4. Result of improper code entry (optional)
--
Choose between a 30-second code lockout, duress output,
a 15-minute code lockout, or no reaction.
* Note: When appears in the instructions, it indicates master code entry.
GETTING STARTED
A master code is required to program the keypad. The default master code is set to "0000." To change a
forgotten master code, go to page 15 and follow the instructions for "MASTER CODE BYPASS" (DAP
jumper).
Once the master code is set, review the programming options and decide exactly what the keypad will do,
including the format of the user access codes as well as how the keypad responds via the relay output,
buzzer and LEDs. Note that in every case the basic steps for programming are:
1. Enter the master code, followed by the key, which puts you in programming mode.
2. Enter the programming options defined in the various sections as needed, followed by the key.
3. Enter the key again to exit programming mode.
Note: A rapid string of 5 beeps and/or 5 LED flashes indicates an error, while 2 beeps indicates that the
entry has been accepted.
WIRING, BASIC DIAGRAM
Enter Master code
Note: For first-time use, Master code is
Confirm
Function
Enter into programming mode
ENTER PROGRAMMING MODE
User ID
00 to 99
0 to 9
Access code
4 to 8 digits
4 to 8 digits
4 to 8 digits
Confirm
Function
Change Master Code
Set/change up to 100 User Codes for relay output #1, with duress feature
Set/change up to 10 User Codes for relay output #2
X X X X
*
0 0 0 0
#
#
#
0
1
2
USER PROGRAMMING
ADDING OR CHANGING MASTER AND USER CODES
Note: No user code may be the same as the master code.
Note: For User ID, key in the number of the user. For Access Code, type in the code for that particular user.
DELETE A USER
To delete a user who has left the company or who no longer has authority to enter the protected area:
Enter Master code Confirm
Function
Enter into programming mode
X X X X
2. Delete code:
EXIT THE PROGRAMMING MODE BY PRESSING THE "
*
" KEY
1. Enter programming mode:
User ID
00 to 99
0 to 9
Confirm
Function
Deletes specific user ID from output #1
Deletes specific user ID from output #2
#
#
Option
Option
1
2
X X X X
#
*
*
*
1
Mantrap control output -- Outputs ground (-) for five seconds after relay output #1 is activated, continues while the door is open.
2
Connect to ground (-) to prevent relay output #1 from operating, or to the mantrap (interlock) control output of another keypad
to disable output #1 while the other keypad is active.
3
Connect to optional N.O. push button or switch.
4
For DC, connect to a regulated power supply with correct polarity, + to +, - to -. For AC, polarity is not important.
WARNING
--
Press the correct option key. If the option key is not used and a "0" is pressed after entering the Master
Code, it could accidentally reprogram the Master Code.
Page 4 Page 13
EG In - Egress -- N.O., ground (
-
)
3
Relay #2 output -- N.O.
Relay #2 output -- COM
Relay #2 output -- N.C.
Relay #1 output -- N.O.
Relay #1 output -- COM
Relay #1 output -- N.C.
(
-
)
(+)
}
1A @ 28VDC, Normally
closed and normally open
dry contacts
}
5A @ 28VDC, Normally
closed and normally
open dry contacts
Tamper
Relay
1
Relay
2
(+) (--)
12-24V AC/DC
Output #1
N.C. COM N.O.
Output #2
N.C. COM N.O.
Egress
In
Keypad
Active
Duress
Output
(--)
Ground
Door
Sensor
Interlock
Tamper
N.C.
O/P 1
Inhibit
ON OFF
DAP
N.C. dry contact.
50mA max.
}
N.C. Tamper
N.C. Tamper
Interlock -- NPN transistor, used with second keypad
1
(
-
) N.O. O/P #1 inhibit
2
(
-
) N.C. Door position sensor input
(
-
) Common Ground - for use with interlock function
Duress O/P -- Transistor Ground (
-
) 100mA@24VDC
Keypad Active O/P -- Transistor Ground (
-
) 100mA@24VDC
12~24
VAC/VDC
4
}