ENFORCER Delayed Egress Timer
SECO-LARM U.S.A., Inc 5 SECO-LARM U.S.A., Inc. 33 5
IMPORTANT
Users and installers of this product are responsible for
ensuring that the installation and configuration of this
product complies with all national, state, and local laws
and codes related to locking and egress devices.
SECO-LARM will not be held responsible for the use of
this product in violation of any current laws or codes.
Relock Modes:
Standard Mode (Default)
The SA-025EQ can operate in three different
relock modes: standard mode, BOCA
mode, and timed mode. In order to switch
between these modes, locate the relock
mode jumper on the circuit board and move
the jumper to the appropriate pins.
Relock mode
jumper
Once the lock has been released, it will remain released until manually relocked by a reset
device connected to the Reset Input. For information on connecting a reset device, see pg. 4,
Wiring Diagram. This reset device is often a momentary spring-loaded key switch.
BOCA Mode
This mode is for use with BOCA (Building Officials Code Administrators) regulations.
Once the lock is released, the door will remain unlocked until the door is closed. Once closed, the
door will still remain unlocked for 30 seconds. If the door is opened at any time during the 30
seconds, the timer will reset. The 30-second timer will restart once the door is closed.
NOTE: The lock status jumper (see pg. 7) must be ON with a door-mounted N.C. magnetic contact
connected to the lock status input terminal for the BOCA mode to operate correctly.
Timed Mode
Once the lock is released, it will remain released for the duration of the set post-delay timer.
To set the post-delay timer see pg. 6, Adjusting the Pre-Delay and Post-Delay.
Standard mode
BOCA mode
Timed mode