SECO-LARM USA SA-025EQ Home Security System User Manual


 
ENFORCER Delayed Egress Timer
10 SECO-LARM U.S.A., Inc.
Sample Application Installation in a Building
In this application, the SA-025EQ is used to delay exit from a building.
Relock mode set to standard mode.
Pre-delay timer set to 15 seconds.
Power-up mode set to automatic relock (DIP Switch 1 OFF).
Nuisance delay set to 0 seconds (DIP Switch 2 and 3 OFF).
Lock status jumper ON.
Security mode jumper OFF.
Local alarm output type jumper ON.
1. A N.C. magnetic contact mounted on a door is connected to the lock status input so the SA-025EQ
knows if the door is opened or closed.
2. A push-to-exit bar is connected to the initiate input. This device will be the primary means of egress.
3. A spring-loaded switch is connected to the reset input. This device will manually reset
the lock.
4. A spring-loaded switch is connected to the pre-delay bypass input. This will allow any authorized
user immediate access to the protected premises.
5. An alarm buzzer is connected to the local alarm output to indicate when the SA-025EQ is in the
process of unlocking a door. The alarm buzzer will remain active for 5 seconds after the door is
unlocked.
6. An electromagnetic lock is connected to the lock relay output.
7. A strobe light is connected to the remote alarm relay output. This device will signal at a remote
location whenever the remote alarm relay output is triggered.
8. The bypass input and free egress input are not used. Jumpers are placed between the bypass input,
free egress input, and positive power input terminal.
Magnetic contact
Push-to-exit bar
Spring-loaded switch
Electromagnetic lock
Alarm buzzer
Strobe light
Power
supply