Sanyo KS1251 Air Conditioner User Manual


 
45
9-2. Air Conditioner Does Not Operate
9-2-1. Circuit breaker trips (or fuse blows)
A. When the circuit breaker is set to ON, it is tripped soon. (Resetting is not possible.)
There is a possibility of ground fault.
Check insulation resistance.
If resistance value is 1Mor less, insulation is defective (“NO”).
B. Circuit breaker trips in several minutes after turning the air conditioner on.
There is a possibility of short circuit.
Measure insulation
resistance of electrical
parts in outdoor unit.
NO
NO
Set circuit breaker to OFF.
*
Measure insulation
resistance of electrical
parts in indoor unit.
1
Remove both power supply wires
and inter-unit wires from terminal
plate in outdoor unit.
Measure insulation resistance
of outdoor unit.
2
Remove inter-unit wires from
terminal plate in indoor unit.
Measure insulation resistance
of indoor unit.
Insulation of
outdoor unit
is defective.
Insulation of
indoor unit
is defective.
WARNING
Check capacity of circuit breaker.
Capacity of circuit breaker is
suitable.
Replace with suitable
one (larger capacity).
Measure resistance of compressor
motor winding.
Measure resistance of outdoor fan
motor winding.
NO
INDOOR
INDOOR UNIT
Terminal
Disconnect
switch
(Field supply)
1
2
3
1
2
3
4
5
6
GG
Grounding
line
(Inter-unit)
Power lines
Terminal
OUTDOOR UNIT
Power supply line
Single-phase, 230/208 V
Fuse
L1
L2
Circuit
breaker
1
Ground
1
2