8-1. Room Temperature Control
Room temperature control is obtained by cycling the compressor ON and OFF under control of the room
temperature sensor in the remote control unit.
The room temperature (and other information) is transmitted every 3 minutes by the remote control unit to
the controller in the indoor unit.
The control circuit will not attempt to turn the compressor ON until the compressor has been OFF for at
least 3 minutes. To protect the compressor from stalling out when trying to start against the high side
refrigerant pressure, the control circuit has a built-in automatic time delay to allow the internal pressure to
equalize.
As a protective measure, the control circuit switches the compressor OFF after 5 minutes or more of com-
pressor operation.
Thermo ON : When the room temperature is above T + 2°F (T°F is set temperature).
Compressor ON
Thermo OFF : When the room temperature is equal to or below set temperature T°F.
Compressor OFF
Set temp.
T+2°F
Signal from remote control unit
Room temp.
More than
5 minutes
Thermo
OFF
Indoor fan
Outdoor fan
Compressor
Set speed
ONONON OFF OFF OFF
ON OFFON ONOFF OFF
3 minutes5 minutes
3 minutes 3 minutes 3 minutes 3 minutes 3 minutes 3 minutes 3 minutes
Thermo
ON
Thermo
OFF
Thermo
ON
Thermo
ON
Thermo
ON
Thermo
OFF
T°F