Samsung NH300WHXEA Heat Pump User Manual


 
36_ Operating advanced function
Operating advanced function
FIELD SETTING MODE
DHW Heating : Code 30✴✴
T(C)
T
U
> T
HP MAX
T
HP MAX
T
HP OFF
T
HP ON
T
U
#3021
#3022
#3023
T(C)
T
U
< T
HP MAX
T
HP MAX
T
U
=T
HP OFF
T
HP ON
#3021
#3023
1
t
0
1
0
DHW
request
Heating
request
DHW(H/P)
operation
#3024
#3025 #3026
1
0
Field Setting Value
Main Menu &
Code
Sub Menu Function Description
Sub
Code
Default Min Max Step Unit
DHW
Code 30✴✴
Domestic Hot Water
Tank
Application ✴✴11 0(No) 0 1(Yes) - -
Heat Pump Max Temp ✴✴21 50 45 55 1 ˚C
Stop ✴✴22 2 2 10 1 ˚C
Start ✴✴23 5 1 20 1 ˚C
Min Operation ✴✴24 5 0 20 1 min
Max Operation ✴✴25 30 5 95 5 min
Interval ✴✴26 3 0 10 0.5 hour
Booster Heater Application ✴✴31 1(On) 0(Off) 1 - -
Delay Time
✴✴32 20 20 95 5 min
Overshoot ✴✴33 0 0 4 1 ˚C
Compensation Temp
✴✴34 10 0 20 1 ˚C
Disinfection Application ✴✴41 1(On) 0(Off) 1 - -
Interval ✴✴42 Fri Mon Sun 1(All) day
Start Time
✴✴43 23 0 23 1
o'clock
Target Temp ✴✴44 70 40 70 5 ˚C
Duration ✴✴45 10 5 60 5 min
Power DHW by User
Input
Timer OFF Function
✴✴51 0(Off) 0 1 - -
Timer Duration
✴✴52 60 30 300 10 min
Solar Panel H/P Combination ✴✴61 0(No) 0(No) 1(Yes) - -
Tu : User set temp.
T(C) : Temp. (Celcius)