Samsung NH300WHXEA Heat Pump User Manual


 
30_ Operating advanced function
Operating advanced function
FIELD SETTING MODE
Field Setting Value(FSV) Table
• Code 10✴✴ : Upper and lower temperature limits of each operation mode of wired remote controller
Heating(Water Out, Room), Cooling(Water Out, Room), DHW(Tank)
• Code 20✴✴ : Water law design and external room thermostat
Heating(2 WL’s for floor & FCU), Cooling(2 WL’s for floor & FCU), WL & Thermostat
types
Field Setting Value
Main Menu &
Code
Sub Menu Function Description
Sub
Code
Default Min Max Step Unit
Remote
Controller
Setting Range
Code 10✴✴
Water Out Temp for Cooling
Max ✴✴11 25 18 25 1 ˚C
Min ✴✴12 16 5 18 1 ˚C
Room Temp for Cooling
Max ✴✴21 30 24 30 1 ˚C
Min ✴✴22 18 18 22 1 ˚C
Water Out Temp for Heating
Max ✴✴31 55 37 55 1 ˚C
Min ✴✴32 25 15 37 1 ˚C
Room Temp for heating
Max ✴✴41 30 24 30 1 ˚C
Min ✴✴42 16 16 22 1 ˚C
DHW Tank Temp
Max ✴✴51 50 50 70 1 ˚C
Min ✴✴52 40 30 40 1 ˚C
Water Law
Code 20✴✴
Outdoor Temp for Water Law
(Heating)
Point
✴✴11 -10 -20 5 1 ˚C
Point
✴✴12 15 10 20 1 ˚C
Water Out Temp for WL1 Heating
(WL1-Floor)
Point
✴✴21 40 40 55 1 ˚C
Point
✴✴22 25 17 37 1 ˚C
Water Out Temp for WL2 Heating
(WL2-Fan Coil Unit)
Point
✴✴31 50 40 55 1 ˚C
Point
✴✴32 35 17 37 1 ˚C
Heating Water Law for Auto Mode WL Type
✴✴41 1(WL1) 1
2(WL2)
- -
Outdoor Temp for Water Law
(Cooling)
Point
✴✴51 30 25 35 1 ˚C
Point
✴✴52 40 35 45 1 ˚C
Water Out Temp for WL1 Cooling
(WL1-Floor)
Point
✴✴61 25 18 25 1 ˚C
Point
✴✴62 18 5 18 1 ˚C
Water Out Temp for WL2 Cooling
(WL2-Fan Coil Unit)
Point
✴✴71 18 18 25 1 ˚C
Point
✴✴72 5 5 18 1 ˚C
Cooling Water Law for Auto Mode WL Type
✴✴81 1(WL1) 1
2(WL2)
- -
External Thermostat Application
#1(Floor) ✴✴91 0(No) 0 1(Yes) - -
#2(FCU) ✴✴92 0(No) 0 1(Yes) - -