Regency U32S-NG5 Indoor Fireplace User Manual


 
9U32S-5 FPI Direct Vent Gas Insert
VENTING
THE APPLIANCE MUST NOT BE
CONNECTED TO A
CHIMNEY FLUE SERVING A
SEPARATE SOLID FUEL
BURNING APPLIANCE.
This appliance is designed to be attached to
two 3" (76mm) co-linear aluminium ex running
the full length of the chimney. The ue length
must be a minimum length of 8 ' (2.44m) and
a maximum of 35' (10.7m). See chart below for
minimum distances from roof. Periodically check
that the vent is unrestricted.
Masonry chimneys may take various contours
which the exible liner will accommodate.
However, keep the exible liner as straight as
possible, avoid unnecessary bending.
The Air Intake pipe must be attached to the inlet
air collar of the termination cap.
Part # Description
948-305 3" Flex - 35 ft.
946-529 Co-linear DV Vertical
Termination Cap
GAS CONNECTION
GAS CONNECTION WARNING:
Only persons licensed to work
with gas piping may make the
necessary gas connections
to this appliance.
1) If the appliance is to be installed into an
existing chimney system, thoroughly clean
the masonry or factory built replace.
2) The appliance is provided with an opening on
the left hand side of the control compartment.
A 3/8" NPT gas supply pipe must be brought
near this inlet hole.
3) Locate the center point where the vent
will pass through the chimney above the
appliance. Move the appliance into the
exact location where it is to be installed.
Ensure that the Insert is level.
INSTALLATION
12" Mantel
3-1/2"
Mantel
47”
(1194mm)
to ceiling
17"
13"
20“
to floor
2
0
12
6
4
810
2
0
12
6
16
4
14
8
18
10
Side View
Top of
Unit
Faceplate
To
p
G
C
L
Gas
Inlet
Alternate Approved Caps
46dva-VC Vertical Termination Cap
46dva-VCH High Wind Cap
46dva-GK 3" Co-linear Adaptor with ashing
In areas of consistently high winds, we
recommend using the Simpson Dura-Vent
System (46dva-GK adapter and 46dva-VCH
high-wind cap).
The Air Intake pipe must be attached to the
inlet air collar of the termination cap.
Due to the extreme heat this replace emits,
the mantel clearances are critical.
Note: A non-combustible mantel may be
installed at a lower height if the
framing is made of metal studs
covered with a non-combustible
board.
Mantel can be installed anywhere in shaded area
or higher using the above scale.
Note: Ensure the paint that is used
on the mantel and the facing is
"heat resistant" or the paint may
discolour.
COMBUSTIBLE MANTEL
CLEARANCES