Regency P121RC-NG Indoor Fireplace User Manual


 
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace
18
INSTALLATION
Vertical Flueing with Two (2) 90
o
Elbows
Option V H
A) 1' (305mm) Minimum 4' (1.22m) Maximum
B) 2' (610mm) Minimum 6' (1.86m) Maximum
C) 3' (914mm) Minimum 9' (2.7m) Maximum
D) 4' (1.22m) Minimum 12' (3.6m) Maximum
E) 5' (1.5m) Minimum 15' (4.5m) Maximum
F) 6' (1.86m) Minimum 17' (5.1m) Maximum
Vertical Flueing with Two (2) 90
o
Elbows
Vertical Flueing with Three (3) 90
o
Elbows
Diagram 9
Diagram 10
Diagram 11
Option V + V1 H H + H1
A) 2' (610mm) Min. 1' (305mm) Max. 2' (610mm) Max.
B) 3' (914mm) Min. 4' (1.22m) Max. 5' (1.5m) Max.
C) 4' (1.22mm) Min. 6' (1.86m) Max. 8' (2.4m) Max.
D) 5' (1.5m) Min. 8' (2.4m) Max. 12' (3.6m) Max.
With the above options, maximum total pipe length if 37 feet with
minimum of 6 feet total vertical and maximum 17 feet total horizontal.
Please note minimum 1 foot between 90
o
elbows is required.
Option V H + H1
A) 1' (305mm) Minimum 2' (610mm) Maximum
B) 2' (610mm) Minimum 4' (1.22m) Maximum
C) 3' (914mm) Minimum 6' (1.86m) Maximum
D) 4' (1.22m) Minimum 8' (2.4m) Maximum
With the above options, maximum total pipe length if 37 feet with
minimum of 4 feet total vertical and maximum 8 feet total horizontal.
Please note minimum 1 foot between 90
o
elbows is required.
With the above options, maximum total pipe length if 37 feet with
minimum of 5 feet total vertical and maximum 12 feet total horizontal.
Please note minimum 1 foot between 90
o
elbows is required.