Regency E21-NG1 Indoor Fireplace User Manual


 
8
Regency E21 Gas Fireplace Insert
HIGH ELEVATION
This unit is approved in Canada for altitude
0 to 4500 ft. (CAN/CGA 2.17-M91) with the
orifi ce supplied.
System Data
For altitude: Natural Gas 0-2000 ft.
Propane: 0-4500 ft.
Burner Inlet Orifi ce Sizes:
Natural Gas Propane
Burner #43 #54
Max. Input Rating
- Natural Gas 23,500 Btu/h
- Propane 22,500 Btu/h
Min. Input Rating
-
Natural Gas
- Natural Gas-
+/-5% 11,750 Btu/h
-Propane +/-5% 11,250 Btu/h
Supply Pressure
Natural Gas min. 5.0" w.c.
Propane min. 12.0" w.c.
Manifold Pressure (High)
Natural Gas 3.8" +/- 0.2" w.c.
Propane 11" +/- 0.2" w.c.
Circulation Fan:
120 VAC, 60 Hz
Variable Speed:
127 CFM, thermally
activated
NATURAL GAS E21-NG1
For alti
tude: 2000 ft - 4500 ft.
Burner Inlet Orifi ce Size:
44 DMS
Max. Input Rating
22,000 Btu/h
Min. Input Rating
+/-5%
11,000 Btu/h
INSTALLATION
GAS CONNECTION
Only persons licensed to work with gas piping
may make the necessary gas connections to
this appliance.
The gas connection is a 3/8" NPT accessible on
the left side of the unit. The gas line connection
may be made of rigid pipe, copper pipe or an
approved fl ex connector. (If you are using rigid
pipe, ensure that the valve can be removed
for servicing.) Since some municipalities have
additional local codes it is always best to consult
with your local authorities and the CAN/CGA
B149 installation code.
For USA installations follow local codes and/or
the current National Fuel Gas Code, ANSI
Z223.1.
When using copper or fl ex connectors use only
approved fi ttings. Always provide a union so that
gas lines can be easily disconnected for burner
or fan servicing. Flare nuts for copper lines and
fl ex connectors are usually considered to meet
this requirement.
Important: Always check for gas leaks
with a soap and water solution or gas
leak detector. Do not use open fl ame
for leak testing.
For minimum and maximum supply pressure
see the System Data table.
1)
If the appliance is to be installed into an
existing chimney system, thoroughly clean
the masonry fi replace that has been chosen
for the Regency Gas Fireplace.
2)
The appliance is provided with an opening on
the left hand side of the control compartment
for the gas line.
Note: During any pressure testing of the gas
supply piping system that exceeds test pressures
of 1/2 psig, this appliance and its individual
shut-off valve must be disconnected from the
piping system. If test pressures equal to or less
than 1/2 psig are used then this appliance must
be isolated from the piping system by closing
its individual manual shut-off valve during the
testing.
CAUTION: If the glass is removed for
servicing, it must be replaced prior to
operating the appliance. The glass must
be fixed in the closed position when
operating.