A. Mantel and Wall Projections
WARNING! Risk of Fire! Comply with all minimum clear-
ances to combustibles as specifi ed. Framing or fi nishing
material closer than the minimums listed must be construct-
ed entirely of noncombustible materials (i.e., steel studs,
concrete board, etc).
Clearance to combustible material under the insert is 1/4
inch (6 mm). Clearance to sides of fi replace opening to
combustibles is 6 inches (152 mm). Clearance from top of
fi replace opening (152 mm) to combustibles extending 1
inch is 6 inches. Clearance from top of fi replace opening
for combustibles extending 1 inch to 12 inches max. is 12
inches. See Figure 11.1.
• Use leveling legs to raise insert minimum 1/4 inch (6 mm)
above combustible material or outer wrap of factory built
fi rebox.
Combustible facings must not extend behind the insert
surround.
11
11
Finishing
Note: All
measurements
in inches.
MEASUREMENTS FROM
TOP EDGE OF UNIT
12 in. MIN.
12 in. MAX.
MANTEL
EXHAUST
VENT PIPE
INLET AIR
VENT PIPE
Figure 11.1 Clearances to Mantels or other Combustibles
above Appliance