Quadra-Fire • QVI-35FB-S • 2178-900 Rev. B • 12/0820
7
7
Installation Preparation
Prepare the existing solid fuel masonry or factory built
non-combustible fi rebox for installation.
A. Inspection and Cleaning
Prior to installing the gas insert:
• Have the chimney and adjacent structure inspected
and cleaned by qualifi ed professionals. Hearth & Home
Technologies recommends that NFI or CSIA certifi ed
professionals, or technicians under the direction of certi-
fi ed professionals, conduct a minimum of a NFPA 211
Level 2 inspection of the chimney.
• Replace component parts of the chimney and fi replace
as specifi ed by the professionals.
• Ensure all joints are properly engaged and the chimney
is properly secured.
• Ensure combustible mantel and surround clearances
comply with applicable codes and regulations for solid-
fuel fi replaces. In the absence of local or regional codes,
refer to NFPA 211.
• Ensure chimney is constructed of non-combustible
materials.
• Ensure chimney is clean and in good working order.
• Ensure that all chimney cleanouts fi t properly to prevent
air leakage into chimney.
B. Flue Damper
Fully lock the solid fuel fi replace’s fl ue damper in the open
position, OR completely remove it.
C. Gas Line
Note: If the factory built fi replace has no gas access hole
provided, an access hole of 1 inch (25 mm) diameter or
less may be drilled through the lower sides or bottom of the
fi rebox in a proper workmanship - like manner. This access
hole must be plugged with non-combustible insulation after
the gas supply line has been installed.
• Install gas line into fi rebox cavity.
• Check local codes and gas line sizing requirements
following NFPA54. See Section 8.
D. Hearth or Hearth Extension
WARNING! Risk of Fire! A hearth or hearth extension (if
present) must comply with either of the following:
• The solid fuel burning fireplace manufacturer’s
specifi cation.
• Local building codes required by authority having
jurisdiction.
• NFPA 211
F. Electrical Outlet Box
An outlet box may be installed in a bottom back corner of
the fi replace to permit fans or other optional accessories
to be used. Alternatively, the supplied power cord may be
routed out onto the hearth to a nearby outlet.
E. Fireplace Conversion Notice
Permanently attach the label with the following warning to
the inside lower back of the fi replace fi rebox into which the
insert is being installed. Silicone or mechanical fasteners
may be required to properly secure the label.
WARNING! Risk of Fire! This fi replace has been con-
verted for use with a gas fi replace insert only and cannot
be used for burning wood or solid fuels unless all original
parts have been replaced, and the fi replace re-approved
by the authority having jurisdiction.