Quadra-Fire QVI-30FB-S Indoor Fireplace User Manual


 
Quadra-Fire • QVI-30FB-S • 2020-910 Rev. H • 6/09
7
3
3
Fireplace Size Requirements
Figure 3.1 Fireplace Opening
NOTE: For actual appliance dimensions refer to Section 15.
B
2 in.
50.8 mm
A
C
TOP VIEW
D
FRONT VIEW
MINIMUM FIREPLACE SIZE
Location
QVI30FB-S
Inches Millimeters
A Front Width 30-1/4 768.4
B Rear Width 19 482.6
C Depth 14-1/8 358.8
D Height 22-1/2 571.5
* NOTE: If exhaust collar on insert and replace damper do not line up, add
4 inches (102 mm) to minimum replace height for bends in vent pipe.
A. Minimum Fireplace Opening
Minimum replace opening requirements are shown in
Figure 5.1.
WARNING! Risk of Fire or Burns! Provide adequate
clearance around air openings and for service access.
Due to high temperatures, the appliance should be locat-
ed out of traf c and away from furniture and draperies.
• The rebrick (refractory), glass doors, screen rails, screen
mesh and log grates can be removed from a factory
built rebox in order to gain minimum gas insert opening
requirements.
Any smoke shelves, shields and baf es may be removed
from the factory built rebox if attached with mechanical
fasteners.
• The metal oor of the solid fuel rebox may be removed to
facilitate the installation of the insert. The appliance may
not be placed directly on the base of the outer wrap, a 1/4
inch airspace must be provided between the insert and
the oor of the outer wrap. Use the levelling legs to raise
the insert a minimum of 1/4 inch. The original replace
may never be returned to solid fuel in this condition.
The sidewalls and top structure of the rebox may not
be altered with the exception of removable baf es and
dampers.
Cutting of any sheet metal parts of the replace in which
the gas replace insert is to be installed is prohibited,
except the oor as tested for and as noted above.