Quadra-Fire CB1200MI-MBK Indoor Fireplace User Manual


 
Page 10
7014-188B
February 3, 2010
R
CB1200-I Pellet Insert
R
R
A
B
C
D
D. Minimum Opening for Masonry and Zero
Clearance Fireplaces for Built-In Using
Rear Shroud
SIDE WALL
MANTEL
D
C
E
A
B
Face Trim
Inches Millimeters
A Louvers to combustible
side wall
6 153
B Insert top to mantel 12 305
C Top to Face Trim 3 76
D Hearth Extension - Front 6 153
E Hearth Extension - Sides 8 203
Inches Millimeters
A Rear Width 22 558
B Depth 15-1/2 393
C
*
Height - Top Vent 25-1/2 647
Height - Rear Vent 22-1/2 571
D Front Width 29-1/4 743
Figure 10.1
Figure 10.2
C. Minimum Clearances To Combustibles for
Masonry and Zero Clearance Fireplaces
*The size of your oor protector choice must be added to
this dimension. If using Quadra-Fire oor protector, Part
811-0730, allow 1-1/2 inches (38mm).
NOTE: A Quadra-Fire oor protector (Part 811-0730) is
available through your dealer to be used as a oor protec-
tor for the section under the insert body only. Floor protec-
tion to front and sides of insert unit must be supplied in
addition to this part.
F. Floor Protection
1. Zero Clearance Installations*
It is necessary to install a oor protection of non-combus-
tible material with a R value of 3.0 (1 inch [25mm] minimum
thickness with a “k” value of 0.58) or a 1 inch (25mm) air
space between insert base and hearth.
2. Non-Zero Clearance Installations*
A non-combustible oor protector is required with a mini-
mum R value of 3.0 (1 inch [25mm] minimum thickness with
a “k” value of 0.58) extending 6 inches (153mm) in front of
the insert and 8 inches (203mm) to each side of the door
opening.
* See alternate oor protection worksheet.
E. Masonry Minimum Opening
Location Inches Millimeters
A Rear Width 22 558
B Depth 13 330
C Height - Top Vent 19-1/2 495
D Front Width 29-1/4 743
A
B
C
D