Quadra-Fire 7100FP-GD-B Indoor Fireplace User Manual


 
September 7, 2007
433-1390D
Page 45
7100FP EPA Woodburning Fireplace
R
B. Outside Air
A source of air (oxygen) is required in order for combustion
to take place. Whatever air is consumed by the re must be
replaced through cracks around windows, under doors, etc.
Most newly constructed houses or existing homes tted with
tightly sealed doors and windows are relatively air tight. In
this case, an outside air source must be made available to
feed combustion air from outside the home.
The 7100FP Fireplace comes equipped with an outside air
intake to feed combustion air from outside the home, along
with an outside air termination cap. The 6 in. (152 mm) solid/
ex pipe is not supplied.
Outside air is required to minimize the effects of negative
pressure within the structure. It is recommended to utilize
the shortest duct run to optimize the performance of the Out-
side Air ex tubing. The outside air inlet thimble should be
positioned above the ground level, and must remain clear
of leaves, debris, ice and/or snow. If you live in an area that
experiences deep snow levels, this must be taken into con-
sideration when determining the height placement above
ground level. It must be unrestricted while unit is in use to
prevent room air starvation which can cause smoke spillage
and an inability to maintain a re. Smoke spillage can also
set off smoke alarms.
C. Clear Space Near the Fireplace
Combustible materials must not be stored on the hearth ex-
tension. Room furnishings such as drapes, curtains, chairs
or other combustibles must be at least 4 ft (1219mm) from
the open front of the replace.
This replace will operate correctly only if adequate
ventilation is provided to allow proper draft to the re-
place system. Hearth & Home Technologies assumes
no responsibility for the improper performance of the
fireplace system caused by inadequate draft due to
environmental conditions, down drafts, tight sealing
construction of the structure, or mechanical exhausting
devices which create a negative air pressure within the
structure where the replace is located.
NOTE: OUTSIDE AIR IS REQUIRED.
An outside air control handle allows you control of the out-
side air inlet. This may be closed only when the replace is
not in use to prevent cold air in ltration. Use of outside air
for combustion is required to conserve heated air within the
structure and to provide make up air to keep the replace
venting properly.
See Figure 44.1, on page 44, for location and operation.
D. Firescreen
A rescreen is optional to control sparks. It must be in place
whenever the replace is in use. Glass doors or rescreens
must not be used to hold burning material inside the re-
place. Only those glass doors speci cally tested and listed
for use with the speci c replace model should be used.
Use both hands to stabilize the screen. Ensure that the
screen is fully attached. Be careful not to stack wood close
to the front or too high that logs could roll out the front. Start
with a small re and adjust your heat to desired setting. If
smoke spillage occurs, put on gloves and then remove the
screen and close the doors. Refer to Troubleshooting Draft
Problems
on page 52.
E. Glass Doors
This replace has been tested and listed for use with doors
as speci ed in Section 12.E. Please refer to the manual
packed with each set of doors for installation instructions.
Fire Risk
Smoke Risk
Doors must be fully opened or fully closed
when operating replace.
Partially opened doors may draw ame, smoke
or heat from replace.
WARNING
CAUTION
Outside air control handle may be warm. Adjust before
lighting re.
Fire Risk
Close rescreen when burning replace.
Do not use rescreen or glass doors to
hold burning material in replace.
Firescreen controls sparks.
Glass may break or burning material may
roll out.
Always wear gloves when installing or
removing the screen as the screen may
become extremely hot while in use.
WARNING