7100FP EPA Woodburning Fireplace
R
Level the Fireplace
Level the replace side-to-side and front-to-back. Shim
with noncombustible material, such as sheet metal, as
necessary. Secure the replace (using the pallet mount-
ing brackets located on either side of the replace) to the
sub oor.
Note: When elevating the fireplace above the hearth
extension the front of the elevated platform must be
protected with a protective metal hearth strip (not included)
as shown in Figure 19.2.
Raised Platform
Floor
2 in.
(51 mm)
1 in. (25 mm) min.
overlap
2 in.
(51 mm)
T
op p
i
ece must over
l
ap
bottom piece
Nail or screw metal strips in place.
Figure 19.2 Protect the Front of an Elevated Platform
Figure 19.1 Position the Protective Metal Hearth Strips
Place the Protective Metal Hearth Strips
Included with your replace you will nd two metal
hearth strips measuring approximately 23 in. x 4 in.
(584 mm x 102 mm). These strips are used to provide
added protection where the replace and the hearth ex-
tension meet.
Slide each metal strip 2 in. (51 mm) under the front edge
of the replace. The individual pieces must overlap each
other by 1 in. (25 mm) minimum in the middle of the re-
place to provide continuous coverage of the oor. See
Figure 19.1. These metal strips should extend from the
front and sides of the replace opening by 2 in. (51 mm).
Nail or screw metal strips in place.
Fire Risk!
Prevent contact with sagging, loose
insulation.
Do NOT install against vapor barriers or
exposed insulation.
WARNING
Fire Risk!
Metal hearth strips MUST be installed.
Sparks or embers may ignite ooring.
WARNING
D. Secure the Fireplace
Position the Fireplace
This replace may be placed on either a combustible or
non-combustible continuous at surface. Follow the in-
structions for framing in Section 3.C. Slide the replace
into position. Be sure to provide the minimum 1 in. (25 mm)
air clearance at the sides and 1/2 in. (13 mm) at back of
the replace assembly. See Section 3.B.
CAUTION
Sharp Edges
Wear protective gloves
and safety glasses during
installation.
Metal strips 2 in. (51mm) under edge of
Fireplace and Hearth Extension and 2 in.
(51mm) on both side of fireplace opening.
Nail or screw metal strips in place.
Pallet Mounting
Brackets
1 in. (25mm) Overlap